DELTABOOSTER_GB01<br />
Function<br />
From the situation on page 3.<br />
The water tank is now almost full. At the moment the level switch (B5) closes, the light<br />
will turn on and the filling stops. A user has just ended his consumption.<br />
� � � � � ��<br />
Unstable<br />
� � H<br />
� � L<br />
Stable<br />
� �<br />
� �<br />
H<br />
L<br />
� �<br />
3<br />
2<br />
1<br />
3<br />
2<br />
1<br />
A<br />
A<br />
A<br />
A<br />
A<br />
A<br />
� �<br />
6<br />
5<br />
4<br />
6<br />
5<br />
4<br />
25.......50.........100...120.....150..175...200<br />
Bar<br />
C<br />
Operation, User No. 2 stops<br />
At the moment a user stops, the pressure will increase by approx. 10 bar and the unused<br />
water, which in this case is the water volume of one pump, will now be lead back to the<br />
water tank through the overflow valve (V1) and the flow valve (B4).<br />
Via a timer (B4) will give signal to stop one pump (P2) which will stop after approx. 15<br />
sec. The stable operation will continue with one user.<br />
When the last user stops the same will happen as described above, and the last pump<br />
will stop. Now the machine is standing with pressure (working pressure) ready for operation.<br />
At the moment a user starts a consumption, the pressure will drop to the level of the<br />
pressure switch (B2) which is approx. 25 bar as standard. That means that the lights (B1)<br />
and (B2) goes out before the start signal to a pump is released, and one pump will start.<br />
If it takes more than approx. 3 sec. to build up the pressure to (B1) level, another pump<br />
will be started. This situation often appears in big pipelines or if there is air in the system.<br />
� �<br />
� �<br />
L<br />
� �<br />
� �<br />
� �<br />
H<br />
� �<br />
� �<br />
4