Function<br />

The diagram illustrates the control functions of the water tank in some given situations -<br />

a, b, c, d, e.<br />

The water temperature is adjusted to 55°C.<br />

The top curve illustrates the actual temperature of the water tank.<br />

Temp Sens, the line indicates that the sensor measures a deviation from the set value.<br />

Adjust, the line indicates that the electronics requires an adjustment of the temperature.<br />

Level Alarm, the line indicates that the level in the water tank has reached the lowest<br />

level (machine stops).<br />

Level High , the line indicates that the water tank is full (stop of water intake).<br />

Level Low, the line indicates that more water is required (start of water intake).<br />

Valve Cold, the line indicates that the solenoid valve with cold water is open.<br />

Valve Hot, the line indicates that the solenoid valve with hot water is open.<br />

* %<br />

* &<br />

* #<br />

* $<br />

;<br />

;<br />

+ �<br />

9 = J A H<br />

J A � F<br />

J = � �<br />

&<br />

$<br />

"<br />

6 A � F 5 A � I<br />

) � K I J<br />

� A L A � ) � = H �<br />

� A L A � 0 E C D<br />

� A L A � � � M<br />

8 = � L A + � � @<br />

8 = � L A 0 � J<br />

= > ? @ A<br />

� = N " I A ?<br />

C<br />

Water Tank, Control<br />

a: There has been no consumption on the machine, and the temperature has therefore<br />

fallen to approx. 20°C. (B5) shows that the water tank is full.<br />

b: A consumption has started. (B6) requires more water. (B7) requires a higher temperature,<br />

the adjustment is activated and Y1 opens.<br />

c: The temperature set is reached. (B5) is still not activated, (Y2) gives access to the<br />

cold water to stabilize the temperature.<br />

d: (B6) requires more water and (B7) requires hot water. The water supply is unsufficient<br />

to fill the tank. After 4 seconds in this condition, the temperature adjustment will be<br />

interrupted and (Y1) as well as (Y2) are kept open irrespective of the water temperature<br />

(on the display of the machine, the temperature light is on).<br />

e: The water supply is insufficient. (B8) is activated and the machine stopped.<br />