DELTABOOSTER_GB01<br />
Function<br />
The control panel has been built-up as a schematic drawing of the DELTABOOSTER.<br />
A number of warning lamps indicate the operational condition of the plant and any fault<br />
situations. The warning lamps are divided into three categories:<br />
Green: indicates a motor or a valve in operation.<br />
Yellow: indicates an activated sensor (pressure switch, flow switch, level switch).<br />
Red: indicates a serious fault (leakage, overheating, low water level).<br />
� �<br />
� �<br />
� �<br />
� �<br />
� �<br />
H<br />
L<br />
� �<br />
3<br />
2<br />
1<br />
� �<br />
� �<br />
A<br />
A<br />
A<br />
� �<br />
� � � � � � � �<br />
� �<br />
If a fault arises, the concerned red light will turn on and the plant stop. The status of the<br />
opereational condition of the machine at the moment the fault arised will be kept until the<br />
current is switched off. Faults on the individual pumps can be by-passed so that the other<br />
pumps can continue their operation. This is achieved by stopping and re-starting the<br />
machine.<br />
Y1 and Y2 turn on when the cold/hot water inlet is open.<br />
Y3 turns on when the relief valve is closed.<br />
E1 and E2 turn on if there is a leakage on the system.<br />
B1 and B2 turn on when the pressure is higher than the setting point of the pressure<br />
switches.<br />
B4 turns on when the flow switches registrate a return of water to tank (over 10 l/min.).<br />
Y4 turns on when the temperature adjustment is on. Flashes if the water supply is insufficient.<br />
E3 turns on in case of an illegal sensor combination. Example: B1 turn on but not B2<br />
(see diagram on page C10).<br />
B7 turns on if the temperature of the water in the water tank is too high, max. 80°C.<br />
B8 turns on if the water level is too low.<br />
B5 and B6 turn on if the water level is either too high or too low.<br />
Mx turns on when the motor pump is in operation.<br />
Qx turns on in the case of an overload or phase breaking (motor protection disconnects).<br />
Kx turns on if the temperature in the windings is too high (over 160°C).<br />
� �<br />
� �<br />
� �<br />
6<br />
5<br />
4<br />
C<br />
Display<br />
8