When installing a DELTABOOSTER plant in a small room, it may be necessay to establish<br />
ventilation of the room if the temperature in the room exceeds 40°C. For the calculation<br />
of the required air renewal, the following points should be considered:<br />
1. A DELTABOOSTER with 2 x 44C3 pumps has an emission of heat of approx.<br />
3,000 watt.<br />
2. The size of the room compared to the machine is very small.<br />
3. The temperature of the ambient air is 40°C.<br />
4. Both pumps are continuously running at max. load.<br />
Calculation formula:<br />
V =<br />
P<br />
R x T<br />
Q x 60,000<br />
Cp x ( T2 - T1)<br />
(l / min)<br />
According to the calculation above, a renewal of 16 m 3 air is required.<br />
A<br />
Calculation of Cooling Air<br />