DELTABOOSTER_GB01<br />

Technical Data<br />

When installing a DELTABOOSTER plant in a small room, it may be necessay to establish<br />

ventilation of the room if the temperature in the room exceeds 40°C. For the calculation<br />

of the required air renewal, the following points should be considered:<br />

1. A DELTABOOSTER with 2 x 44C3 pumps has an emission of heat of approx.<br />

3,000 watt.<br />

2. The size of the room compared to the machine is very small.<br />

3. The temperature of the ambient air is 40°C.<br />

4. Both pumps are continuously running at max. load.<br />

Calculation formula:<br />

V =<br />

P<br />

R x T<br />

Q x 60,000<br />

Cp x ( T2 - T1)<br />

(l / min)<br />

According to the calculation above, a renewal of 16 m 3 air is required.<br />

A<br />

Calculation of Cooling Air<br />

6