6. CONTROL PANEL, CHARGING ADJUSTOR, TIMING RELAY, IGNITION CONTROLMODULE and INVERTER UNIT6.1 Disassembly and assemblyControl panelTiming relayIgnition control moduleModule fixing plate 2Inverter unitCharging regulatorModule fixing plate16.2 Inspectiona. Control panelAC ReceptacleCheck for evidence of burning or contact damage. Replace if either condition exists.DC ReceptacleConnect both terminals of the receptacle with a jumper wire and check if the receptacle is conductivewith two meter leads inserted into the panel; if not conductive, press the “Reset” button on the receptaclepanel and measure it again. If there is still no continuity, replace the DC receptacle.Smart Throttle SwitchThe switch is conductive when “ON” and not conductive when “OFF”.Ignition ModuleRemove the 10P connector from the module and connect one meter lead to the cover and the other leadto the 10P connector and measure resistance.30