12100 OWNER'S MANUALRS485 Communications Circuit• Power limited• Supervised• Voltage: 24 VDC nominal• Current:0.5 amp maximum available for auxiliary power outputs, RS485 circuit and option boards0.4 amp maximum for RS485 circuit• Maximum wire loop resistance: 25 ohms/line• Communications: RS485Addressable Device Circuit• Power limited• Supervised• Voltage: 24 VDC nominal• Maximum Current (shorted): 0.25A• Maximum wire loop resistance: 20 ohms/line• Communications: <strong>System</strong> Sensor• 99 sensors (smoke, heat) max.• 99 monitor and control modules max.RS232 Output (Optional RS232 Board P/N 12103)Power limitedNot supervisedVoltage Range: -15 VDC to +15 VDCMaximum Current (shorted): 0.050ABaud Rate: 4800Maximum wire loop resistance: 25 ohmsDACT Circuit (Optional DACT Board P/N 12105)Power limitedSupervised for short or open circuitMaximum Voltage: 60 VDCMaximum Current (shorted): 0.100 AP/N 447051 Issue I Rev. CII-8