12100 OWNER'S MANUALNAC WIRINGAt the right hand side of the main board the terminal blocks are used for the connection of notificationappliances. Four individual NACs marked A through D are provided and the polarity shown is when theNAC is activated.24K 1/2W<strong>Faraday</strong> P/N 10807Notification Appliance Circuit-Style Y, Class B+Supervised, Power LimitedSee Owner’s Manual forCompatible DevicesPolarity shown in activated conditionNotification Appliance Circuit-Style Z, Class A+Supervised, Power LimitedSee Owner’s Manual forCompatible DevicesSee TypicalWiring aboveSee TypicalWiring aboveNAC Rating:<strong>Alarm</strong> Voltage: 24VDC nominalMax. <strong>Alarm</strong> Current: 1.5AMax. Ripple: 16VACMax. Wire Voltage Drop: 1.0VDCMax. Standby Current: 1.0mANOTE: The maximum current forall NACs is 2.5A.P/N 447051 Issue I Rev. C V-4