12100 OWNER'S MANUALADDRESSABLE DEVICE CIRCUITThe basic configuration of the 12100 control unit includes one addressable device circuit. The circuit caninclude up to 99 sensors and 99 monitor modules. These are polled by the control unit every fewseconds and input or output functions communicated to determine sensor status or module function. Themain processor determines alarm conditions, sensor status and all devices are monitored for troubleconditions.Addressable Device CircuitStyle 4, 6 or 7 Operation(set jumper P1 for proper style)24VDC nominalWire Resistance-20 ohms/lineSupervised, Power LimitedSee Owner’s Manual for Compatible DevicesStyle 6/7Style 4Addressable Device Wiring DiagramsProper connections for UL Listed compatible addressable devices are indicated below. Refer also to theinstruction sheets packed with each device.Sensors and modules may be wired together according to several NFPA defined wiring styles. The wiringstyle that is appropriate for your installation should be determined from the relevant building codes andthe Authority Having Jurisdiction.P/N 447051 Issue I Rev. C V-6