12100 OWNER'S MANUALStyle 7 may be used where it is required that a single break or short in the circuit does not cause anymodules to stop functioning.ADDRESSABLE DEVICE CIRCUITWIRING / OPERATION COMPARABLE TO NFPA STYLE “7”SUPERVISED,POWERLIMITEDEACH CIRCUIT MUST HAVETWO ASSOCIATEDISOLATOR MODULES WITHWIRING ENCLOSED INCLOSED NIPPLEDCONDUIT.EACH DEVICE MUST HAVETWO ASSOCIATED ISOLATORMODULES WITH WIRINGENCLOSED IN CLOSEDNIPPLED CONDUIT.EACH DEVICE MUST HAVETWO ASSOCIATED ISOLATORMODULES WITH WIRINGENCLOSED IN CLOSEDNIPPLED CONDUIT.SUPERVISED,POWERLIMITED*Note:Any combination of Sensors, Monitor Modules, or <strong>Control</strong> Modules up to a maximum of 99 Sensors and99 Modules. Maximum of 1 device between Isolator Modules.When using the 9298 or 9299 Isolator Base, it will be wired in place of a 9160 and the addressablesensor shown in the wiring above (one 9160 Isolator is required per sensor with an isolator base).P/N 447051 Issue I Rev. C V-10