12100 OWNER'S MANUALWIRING SEPARATIONAll high voltage and non-power limited wiring must be kept separate from power limited wiring. A ¼”separation must be maintained, with high voltage and non-power limited wiring running in separateconduit openings from power limited wiring.AC13E2*FA. Non-power limited - High Voltage(AC power) or BB. Non-power limited - High Voltage(AC power) or AC. Power limitedD. Non-power limited(Battery If external enclosure required)E. Non-power limited(Phone line)F. Power limited or GG. Power limited or FBDGPRIMARY AND SECONDARY POWER WIRINGThe AC main connections and the battery connections must be made along the left-hand side of theboard. Route all high voltage and non-power limited wiring together and away from power limited wiring.120VAC 60Hz1.3A max., SupervisedNon-Power LimitedACNGNDKeep All Non-Power Limited WiringSeparate from Power Limited Wiring24V Battery Set(7 to 38AH)SupervisedNon-Power LimitedP/N 447051 Issue I Rev. C V-2