The following steps must be followed when installing the 4XTMF module:1. Remove all power (AC and DC) from the FACP before installing 4XTMF2. Cut jumper JP6 on the main circuit board to allow the control panel to supervisethe 4XTMF module3. Carefully plug the connectors on the 4XTMF module into connectors J10 and J11on the <strong>MS</strong>-<strong>9600</strong> main circuit board, being careful not to bend any pins4. Secure 4XTMF module to standoffs with supplied screws.5. Reapply power to the FACP6. For proper 4XTMF operation, the output relays must be programmed for thefactory default settings as shown on the PC board silkscreen: Alarm Relay,Trouble Relay and Supervisory Relay7. When the installation has been complete, enable the 4XTMF module by slidingthe disconnect switch to the left8. Test system for proper operationStandoffTB3JP3StandoffTB4 TB5 TB6 TB74XTMFJ10 & J11 ConnectorsJ10CUT TOMONITOR 4XTM4XTM OPT BDJ11JP6JP5Cut Jumper JP6J2OPT DACTJ17J16J6J8SW1<strong>MS</strong>-<strong>9600</strong>CB1LCD DISPLAYTB1 TB2HOT NEUT EARTH +BATTERY-KEYPAD I/FJ79604xtm1.cdrFigure 2.10 4XTMF Connectors to <strong>MS</strong>-<strong>9600</strong> ConnectorsNOTE: Jumper JP5 on the <strong>MS</strong>-<strong>9600</strong> main circuit board can be used to configure the FACPsupervisory relay for operation with the 4XTMF module. The supervisory relay must beprogrammed as shown on the main circuit board silkscreen (TB5, Terminals 4, 5 & 6).Cutting JP5 will allow the 4XTMF to generate a trouble if the supervisory contact opensLeaving JP5 in will prevent generation of a trouble if the supervisory contact opens2.6.2 Auxiliary Trouble Input (J16 & J17)Auxiliary Trouble Inputs 1 (J17) and 2 (J16), which are located on the <strong>MS</strong>-<strong>9600</strong> maincircuit board, can be used to monitor for trouble conditions on auxiliary equipment suchas power supplies. J16 and/or J17 can be connected to any open collector troubleoutput on the auxiliary equipment. The <strong>MS</strong>-<strong>9600</strong> control panel will indicate a troublecondition if a trouble is sensed at the Auxiliary Trouble Inputs.If the 4XTMF Module is installed and jumper JP6 on the <strong>MS</strong>-<strong>9600</strong> has been cut tosupervise it, Auxiliary Trouble Input 1 (J17) will monitor the 4XTMF for troubleconditions.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!