Functionsand characteristicsRemote operation 0Remote ON / OFFPB100798-56Electrical closing pushbutton (BPFE)Located on the front panel, this pushbutton carries out electrical closing of the circuitbreaker. It is generally associated with the transparent cover that protects access tothe closing pushbutton.Electrical closing via the BPFE pushbutton takes into account all the safety functionsthat are part of the control/monitoring system of the installation.The BPFE connects to the closing release (XF) in place of the COM module.DB101167Electrical closing pushbutton (BPFE).Remote reset after fault tripElectrical reset after fault trip (Res)Following tripping, this function resets the "fault trip" indication contacts (SDE) andthe mechanical indicator and enables circuit breaker closing.Power supply: 110 / 130 V AC and 200 / 240 V AC.DB101169Automatic reset after fault trip (RAR)Following tripping, a reset of the mechanical indicator (reset button) is no longerrequired to enable circuit-breaker closing. The mechanical (reset button) andelectrical (SDE) indications remain in fault position until the reset button is pressed.50