YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Master</strong> <strong>Drives</strong><strong>CBD</strong>05/20/993 Connecting-up3.1 Connecting-up the bus cableAdapter <strong>Board</strong>LEDGreenYellowRed<strong>CBD</strong>.5.4.3 .2 .1X438TOPV+CAN+ShieldCAN-V-Fig. 3.1Front view of <strong>CBD</strong> with diagnostic LEDs, terminal strip X438 and bus connenctorThe bus connector for terminal strip X438 is supplied loose. These loose components can also be individually orderedfrom Phoenix Contact or Messrs. Phoenix Contact GmbH & Co (bus connector):Order designation:Phoenix number:Combicon MSTB 2.5/5-ST-5.08-AU (cable side-sockets)Cable meeting DeviceNet specifications must be used.Thin cable: Belden 3084AThick cable: Belden 3082A or 3083A or 3085ARelation of DeviceNet Data Rate and Cable Distances:Data Trunk Distance Drop LengthRate (thick Cable) Maximum drop Cumulative125K 500m (1640 ft) 6m (20 ft) 156m (512 ft)250K 250m (820 ft) 6m (20 ft) 78m (256 ft)500K 100m (328 ft) 6m (20 ft) 39m (128 ft)NOTE: Thin cable may be used as trunk. Maximum distance is 100 meters (328 feet) for any baud rate.10 Siemens AG 477 759 4070 76 J AA-74<strong>SIMOVERT</strong>MASTERDRIVES Betriebsanleitung/OperatingInstructions