<strong>Master</strong> <strong>Drives</strong><strong>CBD</strong>05/20/994 Data transfer via DeviceNet4.2 Parameter area (PKW)4.2.1 Use of PKW object4.2.1.6 Parameter value (PWE)PWE Example 2: Set value of parameter P554.1 = 3001 hexThis example details the decoding of the task PWE of example 2 in the Use of PKW object section 4.2.1previously. Since the response ID of the PKW was 4, the parameter is a 16 bit parameter and the value iscompletely contained in PWE1. If the response ID of the PKW had been 5, the parameter would have been a 32bit parameter and the value would have been contained in PWE1 and PWE2.(PWE): P554 (=22A hex): Source for the ON/OFF1 command (control word 1, bit 0)Change the parameter value with index 1 to 3001.Low word(PWE1)Parameter value (PWE)Byte 1 Byte 0Bit No.: 15 8 7 0Hex value 3 0 0 1High word(PWE2)Byte 3 Byte 2Bit No.: 31 24 23 16Hex value 0 0 0 0Bits 0..15:Bits 16..31:Fig. 4.3Parameter value for 16-bit parameter or low component for 32-bit parameterValue = 0 for 16-bit parameter or high component for 32-bit parameterExamples, parameter valueSiemens AG 477 759 4070 76 J AA-74 29<strong>SIMOVERT</strong>MASTERDRIVES Betriebsanleitung/OperatingInstructions