13.07.2015 Views

Example of installation & commissioning guide

Example of installation & commissioning guide

Example of installation & commissioning guide

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

InstallationPreparing the siteRear connectionProvide a minimum space <strong>of</strong> 1200 mm behind the switchboardto allow complete opening <strong>of</strong> the rear doors and theintervention <strong>of</strong> an operator.A minimum space <strong>of</strong> 1200 mm (1500 mm for 4 pole NW40b/50/63 devices) must be arranged at the front <strong>of</strong> theswitchboard to allow complete opening <strong>of</strong> doors and handling<strong>of</strong> a device using a fork-lift truck.Provide 500mm above the switchboard for Horizontal busbarfishplating.Ground fastening points layout■ rear connection depth 1000/1200<strong>Example</strong>: switchgear cubicle + compartment■ rear connection depth 1400<strong>Example</strong>: switchgear cubicle L650 D600 + 2 rearcompartments L650 D400: recommended fi xing point: compulsory fi xing point15 Okken Schneider Electric

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!