Table 4: Installer Configuration Menu (Part 1 of 7)ParameterAppearingon DisplayDescription <strong>and</strong> Default Selection OptionsPswrdSets the protective accesspassword to prevent unauthorizedaccess to the Installer ConfigurationMenu.Default: 0Note: The default setting does notlock out access to the InstallerConfiguration Menu.BI1 Configuration of Binary Input 1.Default: NoneRange: 0 to 1,000(None): No function is associated with an input.(Rem NSB): Remote Night Setback (NSB) via a time clock input, anoccupancy sensor, or from a voltage-free contact.Contact open = Occupied; contact closed = Unoccupied.(MotionNO*): Temporary occupancy request via a motion detectorinput. Contact open = Unoccupied. When the contact closes, thethermostat controller goes into the Occupied mode for a specifiedTOccTime. Once the TOccTime begins, the thermostat controllerremains in the Occupied mode if the contact is open, until theTOccTime expires. Advanced PIR occupancy functions using aNormally Open (N.O.) or Normally Closed (N.C.) remote PIR motionsensor.(MotionNC*): Temporary occupancy request via a motion detectorinput. Contact closed = Unoccupied. When the contact opens, thethermostat controller goes into the Occupied mode for a specifiedTOccTime. Once the TOccTime begins, the thermostat controllerremains in the Occupied mode if the contact is closed, until theTOccTime expires. Advanced PIR occupancy functions using aNormally Open (N.O.) or Normally Closed (N.C.) remote PIR motionsensor.(Window): Cancels the thermostat controller heating or coolingaction when a window is open. The fan operation is only affected ifthe Fan Menu parameter is set to (4): On-Auto, <strong>and</strong> Auto is theselected fan mode. A Window alarm is displayed indicating that thewindow needs to be closed to resume heating or cooling. Theheating <strong>and</strong>/or cooling outputs are enabled only when the contact isclosed.* These settings disable any local override function. For PIRmodels, see the Occupancy Sensor Operation – <strong>T60xDFH</strong>-<strong>4+PIR</strong><strong>Series</strong> <strong>Thermostat</strong> Controllers section.14<strong>T60xDFH</strong>-4 <strong>and</strong> <strong>T60xDFH</strong>-<strong>4+PIR</strong> <strong>Series</strong> <strong>Thermostat</strong> Controllers with Dehumidification <strong>and</strong> OccupancySensing Capability Installation Instructions

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!