H2.2 - VIBRATION<br />
SENSOR ADAPTATION<br />
On request, our <strong>motors</strong> can be fitted with<br />
tapped holes (for SPM type sensor) on<br />
faceplates, to take the vibration sensors (not<br />
supplied).<br />
The adaptors form a connection with the<br />
snap-on transmitter.<br />
H2.3 - DRAINING<br />
CONDENSATION WATER<br />
To drain off any moisture that may have<br />
accumulated inside during cooling of the<br />
machine, drain holes are provided at the<br />
lowest points of the enclosure, depending on<br />
the operating position (IM etc). The holes<br />
may be sealed in various ways:<br />
- standard: with plugs<br />
- on request: with screws or siphon<br />
Opening the holes periodically should be<br />
part of the regular maintenance procedure.<br />
Being specially designed for harsh<br />
environments, they are fitted with a PVC seal<br />
after undergoing the following surface<br />
treatments:<br />
1 - zinc: 15 μm Zn<br />
2 - silver for very corrosive environments:<br />
2 μm Cu + 30 μm Ag<br />
H2.4 - TAPPED HOLES FOR<br />
POSITIONING<br />
Tapped holes for positioning can be made on<br />
the motor feet in order to make it easier to<br />
adjust and align the motor.<br />
They have a metric thread which can also be<br />
created to suit another standard diameter on<br />
request.<br />
H2.5 - RADIAL SEAL<br />
When a motor needs to be mounted in the<br />
vertical position, shaft end facing up (position<br />
IM 1031, 2031 and 3031 for example) and its<br />
shaft end is not correctly protected by the driven<br />
machine against rain or water splashes,<br />
it is advisable to use an optional radial seal<br />
on the drive end to avoid water getting into<br />
the motor around the shaft.<br />
92<br />
3-<strong>phase</strong> <strong>TEFV</strong> <strong>induction</strong> <strong>motors</strong><br />
<strong>ATEX</strong> <strong>GAS</strong> - <strong>Zones</strong> 1 & 2<br />
Optional features<br />
H2 - Mechanical options<br />
Frame size<br />
Non-sparking<br />
LSN/FLSN<br />
Increased safety<br />
LSE/FLSE<br />
Flameproof<br />
FLSD<br />
80 to 132 mm l l -<br />
160 to 200 mm l l m<br />
250 mm and above l l m<br />
l available m please consult Leroy-Somer<br />
Radial seal<br />
Tapped holes for<br />
positioning<br />
Casing interior<br />
Bearing housing<br />
Bearing<br />
Shaft