H2.6 - FORCED VENTILATION<br />
The <strong>ATEX</strong> <strong>motors</strong> described in this catalogue<br />
are approved to be supplied with frequency<br />
inverters.<br />
This type of application sometimes requires<br />
the mounting of a forced ventilation unit for<br />
use at low speed (temperature rise) or at<br />
high speed (noise), in addition to the thermal<br />
protection (winding and DE shield).<br />
The mounting of an axial forced ventilation<br />
unit is recommended for <strong>motors</strong> ≥ frame<br />
size 160.<br />
Safety conditions: The forced ventilation<br />
unit is controlled by the power supply and<br />
should have the same degree of flameproof<br />
protection as the FLSD motor.<br />
To adapt the motor to the application, it is<br />
necessary to inform the manufacturer of the<br />
operating characteristics (speed range,<br />
voltage, frequency, etc).<br />
H2.7 - ENCODERS<br />
All our "d", "e" and "n" safety <strong>motors</strong> can be<br />
fitted with an <strong>ATEX</strong>-certified incremental<br />
encoder with a protection level II 2GD<br />
Ex d IIC.<br />
This pulse generator supplies a number of<br />
pulses proportional to the motor speed. It can<br />
be supplied with a D.C. voltage of 5 V +/- 10%<br />
or 11-30 V regulated.<br />
H2.8 - ROLLER BEARINGS<br />
For high radial forces, it is possible to adapt<br />
roller bearings to the motor DE shield from<br />
frame size 160 upwards.<br />
H2.9 - FLYING LEADS<br />
Motors can be fitted with flying leads<br />
consisting of multicore cables or single-core<br />
cables for high currents.<br />
The earthing is included in the sheathed<br />
cable output.<br />
Accessories (thermal protection, space<br />
heaters, etc) are usually connected using<br />
another multicore cable.<br />
3-<strong>phase</strong> <strong>TEFV</strong> <strong>induction</strong> <strong>motors</strong><br />
<strong>ATEX</strong> <strong>GAS</strong> - <strong>Zones</strong> 1 & 2<br />
Optional features<br />
H2 - Mechanical options<br />
The drive encoder lines per revolution should<br />
be specified (at the time of ordering): 1024 or<br />
4096 (for the incremental encoder) and 8192<br />
(for the absolute encoder).<br />
Please consult Leroy-Somer.<br />
Caution: Motors with flying leads must be<br />
connected in an area with a protection type<br />
compatible with the installation zone.<br />
93