11.12.2012 Views

MDC Manual 1109KB - Red Lion Controls

MDC Manual 1109KB - Red Lion Controls

MDC Manual 1109KB - Red Lion Controls

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

TROUBLESHOOTING GUIDE (Cont’d)<br />

PROBLEMS POSSIBLE CAUSE REMEDIES<br />

UNIT WILL NOT ENTER JOG MODE 1. R-STOP, F-STOP inputs wired incorrectly.<br />

UNIT INDICATES ZERO SPEED<br />

(MOTOR RUNNING)<br />

MOTOR WILL NOT RUN WITH<br />

<strong>MDC</strong> IN “RUN” MODE<br />

“NO FEEDBACK” MESSAGE<br />

DISPLAYED/UNIT ENTERS<br />

STOP MODE<br />

2. Unit in Program mode.<br />

3. Unit is in RUN mode.<br />

1. No feedback signal.<br />

2. Type of input signal incorrectly selected.<br />

3. Scaling parameters programmed incorrectly.<br />

PPR, MAX RPM too large or DSP UNIT too small.<br />

1. Motor or Drive problem.<br />

2. Internal/External jumper for Drive Output in wrong<br />

position.<br />

3. <strong>MDC</strong> Isolated Drive Output improperly calibrated.<br />

4. Speed or Ratio setpoint zero or too low.<br />

5. In Follower mode and Lead input is zero.<br />

1. No feedback signal present.<br />

2. Drive improperly calibrated.<br />

3. <strong>MDC</strong> Isolated Drive Output improperly calibrated.<br />

4. Large “dead band” in drive and motor response at<br />

low speed.<br />

-43-<br />

1. R-STOP and F-STOP inputs must be held low<br />

or tied to comm. to enter JOG mode.<br />

2. JOG is disabled. Exit the programming module.<br />

3. Place unit in STOP mode.<br />

1. Check sensor connection. Verify power to sensor.<br />

2. Check DIP switch setting on side of unit.<br />

3. Check parameters in Program Scaling Menu.<br />

Verify correct FB freq. in Program Diagnostics<br />

Menu TEST DRV OUT.<br />

1. Make sure motor and drive operate independent<br />

of <strong>MDC</strong>.<br />

2. Refer to Installation and Connections section of<br />

manual.<br />

3. See Isolated Drive Output Calibration section<br />

of manual. Verify operation using Program<br />

Diagnostics Menu TEST DRV OUT.<br />

4. Check speed/ratio Setpoint 1 and 2.<br />

5. Verify by programming a DISPLAY for Lead<br />

frequency.<br />

1. Check sensor connection. Verify power to sensor.<br />

2. See drive manual.<br />

3. See Isolated Drive Output Calibration section<br />

of manual.<br />

4. Disable Feedback Loss Detection in the<br />

Program Options Menu.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!