Chapter 6. Basic Operation<br />
• If setting frq with volume resistance on the loader and commanding operation with RUN key on the loader<br />
No. Indication Operation & description<br />
1<br />
-. Target frequency, the first code of Drive Group when turning it on.<br />
-. Press UP() key three times.<br />
2<br />
-. Moved to a code to change a frequency setting mode<br />
-. Press FUNC key.<br />
3<br />
-. The current frequency setting mode is set to 1(terminal)<br />
-. Press DOWN () key.<br />
4<br />
-. Operation command mode may be changed to 0(RUN key of the loader).<br />
-. Press FUNC key twice.<br />
5<br />
-. It displays drv and operation command mode is changed to RUN key.<br />
-. Press UP() key once.<br />
6<br />
-. Moved to frequency setting mode(Frq) code.<br />
-. Press FUNC key.<br />
7<br />
-. Frequency setting mode is changed to 0(keypad of the loader).<br />
-. Press UP() key two times.<br />
8<br />
-. Frequency setting mode may be changed to 3(loader’s volume resistance).<br />
-. Press FUNC key twice.<br />
9<br />
-. It displays Frq and frequency setting mode is changed to loader volume.<br />
-. Turn the loader volume to set to 10.00 in either Max or Min direction.<br />
10<br />
-. Press RUN key. FWD(forward run) lamp of the inverter display blinks and<br />
accelerating frequency is displayed on the LED.<br />
-. When run frequency 10Hz is reached, it is displayed as shown left.<br />
-. Press STOP key.<br />
11<br />
-. FWD(forward run) lamp of the inverter display blinks and decelerating frequency is<br />
displayed on the LED.<br />
-. When run frequency 10Hz is reached, FWD(forward run) lamp is out and target<br />
frequency(10.00) is displayed on the LED.<br />
Wiring diagram<br />
Operating pattern<br />
220 Vac<br />
L1 (R)<br />
L2 (S)<br />
U<br />
V<br />
M<br />
10 Hz<br />
(T)<br />
P<br />
P1<br />
W<br />
SHFT<br />
RUN<br />
Frequency<br />
RUN<br />
N<br />
G<br />
FUNC<br />
STOP<br />
STOP/RST<br />
6-3