20.03.2018 Views

Manual iE5

Manual iE5

Manual iE5

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Chapter 7. Function List<br />

• PG Group<br />

Display Name<br />

Min/Max<br />

range<br />

P13 DC brake start 0 ~ 200<br />

voltage [%]<br />

P14 DC brake start 0 ~ 60<br />

time<br />

[sec]<br />

P15 Jog frequency 0 ~ 200<br />

[Hz]<br />

P16 Max<br />

40 ~ 200<br />

frequency [Hz]<br />

Description<br />

It sets the amount of DC voltage before a motor<br />

starts to run. Motor rated current(P43)<br />

It applies the current to a motor for the set time<br />

before motor accelerates.<br />

It sets the frequency for jog operation. It can not<br />

be set above the max frequency(P16).<br />

This parameter sets the upper limit frequency.<br />

It is frequency reference for Accel./Decel.<br />

Adj.<br />

Factory<br />

during<br />

defaults<br />

run<br />

Page<br />

50 X 10-2<br />

0.0 X<br />

10.00 O 10-3<br />

60.00 X 9-8<br />

Note<br />

If changing the max frequency, all other<br />

frequency parameters but P17(base frequency)<br />

would be changed to the frequency if they are<br />

above the new max. frequency.<br />

P17 Base<br />

frequency<br />

30 ~ 200<br />

[Hz]<br />

P18 Start<br />

0.1 ~ 10<br />

frequency [Hz]<br />

P19 Torque boost 0 ~ 1<br />

selection<br />

P20 Forward<br />

torque boost<br />

P21 Reverse<br />

torque boost<br />

0 ~ 15<br />

[%]<br />

P22 V/F pattern 0 ~ 1<br />

The inverter outputs its rated voltage to the 60.00 X 9-11<br />

motor at this frequency.<br />

The inverter starts to output its voltage at this 0.5 X<br />

frequency.<br />

It is lower frequency limit of frequency(Hz).<br />

0 <strong>Manual</strong> torque boost<br />

0 X 9-13<br />

1 Auto torque boost<br />

Torque boost amount of motor during forward 5.0 X<br />

run, based on max. output voltage.<br />

Torque boost amount of motor during reverse 5.0 X<br />

run based on max. output voltage.<br />

0 Linear 0 X 9-11<br />

1 Square<br />

9-12<br />

7-4