9.3 Installed dimensions<br />

A S<br />

A V<br />

Fig. 34 Installation room for <strong>Logano</strong> <strong>SK645</strong> and <strong>SK745</strong><br />

boilers<br />

1) For the <strong>SK745</strong> 1400 kW and 1850 kW, the control unit is<br />

mounted on the l.h. or r.h. side<br />

1)<br />

A H<br />

A S<br />

6 720 640 417-27.1il<br />

<strong>Logano</strong> Boiler size Clearance A H Clearance A V 1)<br />

<strong>SK645</strong><br />

<strong>SK745</strong><br />

1) Observe dimension L BR (burner length) relative to clearances A V and A S (on the closure side of the burner door)<br />

Installation location<br />

When installing your boiler maintain the<br />

recommended minimum dimensions. Select<br />

the recommended wall clearances to enable<br />

easy access for installation, maintenance and<br />

service work.<br />

Site the boiler only in rooms that comply with<br />

the local regulations appertaining to the<br />

siting of boilers. The room must be large<br />

enough to ensure access to the boiler in line<br />

with local regulations.<br />

Clearance A S<br />

[kW] [mm] [mm] [mm]<br />

120–300 1000 2000 250 + L BR<br />

360–600 1000 2100 250 + L BR<br />

730–1200 1000 2200 250 + L BR<br />

1400–1850 2)<br />

Tab. 21 Specified wall clearances<br />

2) Allow for an additional 230 mm on the side where the control unit is mounted.<br />

1000 2500 250 + L BR<br />

6 720 646 816 (10/2010) – Technical guide <strong>Logano</strong> <strong>SK645</strong> and <strong>SK745</strong> 51<br />