9.3 Installed dimensions<br />
A S<br />
A V<br />
Fig. 34 Installation room for <strong>Logano</strong> <strong>SK645</strong> and <strong>SK745</strong><br />
boilers<br />
1) For the <strong>SK745</strong> 1400 kW and 1850 kW, the control unit is<br />
mounted on the l.h. or r.h. side<br />
1)<br />
A H<br />
A S<br />
6 720 640 417-27.1il<br />
<strong>Logano</strong> Boiler size Clearance A H Clearance A V 1)<br />
<strong>SK645</strong><br />
<strong>SK745</strong><br />
1) Observe dimension L BR (burner length) relative to clearances A V and A S (on the closure side of the burner door)<br />
Installation location<br />
When installing your boiler maintain the<br />
recommended minimum dimensions. Select<br />
the recommended wall clearances to enable<br />
easy access for installation, maintenance and<br />
service work.<br />
Site the boiler only in rooms that comply with<br />
the local regulations appertaining to the<br />
siting of boilers. The room must be large<br />
enough to ensure access to the boiler in line<br />
with local regulations.<br />
Clearance A S<br />
[kW] [mm] [mm] [mm]<br />
120–300 1000 2000 250 + L BR<br />
360–600 1000 2100 250 + L BR<br />
730–1200 1000 2200 250 + L BR<br />
1400–1850 2)<br />
Tab. 21 Specified wall clearances<br />
2) Allow for an additional 230 mm on the side where the control unit is mounted.<br />
1000 2500 250 + L BR<br />
6 720 646 816 (10/2010) – Technical guide <strong>Logano</strong> <strong>SK645</strong> and <strong>SK745</strong> 51<br />