outlet port. Therefore, keeping the flow constant while<br />
the temperature changes. This can be done in two different<br />
ways depending on the valve manufacturer. See below<br />
Fig. 17 for valves manufactured by Honeywell.<br />
TO UNIT<br />
GENERATOR<br />
HOT WATER<br />
SUPPLY<br />
HOT WATER<br />
RETURN<br />
FIG. 17 – DIVERTING SERVICE FOR<br />
HONEYWELL VALVE<br />
For Honeywell valves, the hot water supply enters the<br />
valve at the “common” connection. The hot water outlet<br />
to the generator is sometimes marked “A” or is unmarked.<br />
The bypass connection is sometimes marked<br />
“B” or it may also be unmarked.<br />
YORK INTERNATIONAL<br />
3-WAY DIVERTING<br />
CONTROL VALVE<br />
BYPASS<br />
FOR HONEYWELL VALVE<br />
TO<br />
GENERATOR<br />
FROM<br />
GENERATOR<br />
INLET<br />
LD00944<br />
LD04747<br />
DIVERGING FLOW<br />
PLUG UP PLUG DOWN<br />
(fastened to valve body)<br />
TO BYPASS<br />
FORM <strong>155.16</strong>-<strong>N3</strong><br />
See Fig. 18 for installing valves manufactured by Fisher.<br />
For Fisher valves the hot water supply enters the valve<br />
at the marked “inlet” connection and exits the valve to<br />
go to the generator at the marked “unit” connection.<br />
The bypass connection is sometimes marked “bypass”.<br />
INLET AND OUTLET HOT WATER PIPING<br />
FIG. 18 – DIVERTING SERVICE FOR FISHER VALVES / DETAIL OF FISHER VALVE<br />
Fig. 19 is a sample of a hot water piping arrangement<br />
for a YORK <strong>IsoFlow</strong> TM absorption chiller depicting a<br />
Fisher 3-way hot water control valve.<br />
The following is a description of each component on the<br />
hot water supply/return line to the unit.<br />
Manual Block Valves – These valves are installed,<br />
one on the supply line and one on the return line, to<br />
manually shut off hot water to the unit, thus allowing<br />
ease of serviceability if required.<br />
3-WAY DIVERTING<br />
CONTROL VALVE<br />
HOT WATER<br />
SUPPLY<br />
BYPASS<br />
TO GENERATOR<br />
HOT WATER<br />
FROM<br />
RETURN<br />
GENERATOR<br />
FOR FISHER VALVES<br />
LD00945<br />