outlet port. Therefore, keeping the flow constant while<br />

the temperature changes. This can be done in two different<br />

ways depending on the valve manufacturer. See below<br />

Fig. 17 for valves manufactured by Honeywell.<br />

TO UNIT<br />

GENERATOR<br />

HOT WATER<br />

SUPPLY<br />

HOT WATER<br />

RETURN<br />

FIG. 17 – DIVERTING SERVICE FOR<br />

HONEYWELL VALVE<br />

For Honeywell valves, the hot water supply enters the<br />

valve at the “common” connection. The hot water outlet<br />

to the generator is sometimes marked “A” or is unmarked.<br />

The bypass connection is sometimes marked<br />

“B” or it may also be unmarked.<br />

YORK INTERNATIONAL<br />

3-WAY DIVERTING<br />

CONTROL VALVE<br />

BYPASS<br />

FOR HONEYWELL VALVE<br />

TO<br />

GENERATOR<br />

FROM<br />

GENERATOR<br />

INLET<br />

LD00944<br />

LD04747<br />

DIVERGING FLOW<br />

PLUG UP PLUG DOWN<br />

(fastened to valve body)<br />

TO BYPASS<br />

FORM <strong>155.16</strong>-<strong>N3</strong><br />

See Fig. 18 for installing valves manufactured by Fisher.<br />

For Fisher valves the hot water supply enters the valve<br />

at the marked “inlet” connection and exits the valve to<br />

go to the generator at the marked “unit” connection.<br />

The bypass connection is sometimes marked “bypass”.<br />

INLET AND OUTLET HOT WATER PIPING<br />

FIG. 18 – DIVERTING SERVICE FOR FISHER VALVES / DETAIL OF FISHER VALVE<br />

Fig. 19 is a sample of a hot water piping arrangement<br />

for a YORK <strong>IsoFlow</strong> TM absorption chiller depicting a<br />

Fisher 3-way hot water control valve.<br />

The following is a description of each component on the<br />

hot water supply/return line to the unit.<br />

Manual Block Valves – These valves are installed,<br />

one on the supply line and one on the return line, to<br />

manually shut off hot water to the unit, thus allowing<br />

ease of serviceability if required.<br />

3-WAY DIVERTING<br />

CONTROL VALVE<br />

HOT WATER<br />

SUPPLY<br />

BYPASS<br />

TO GENERATOR<br />

HOT WATER<br />

FROM<br />

RETURN<br />

GENERATOR<br />

FOR FISHER VALVES<br />

LD00945<br />

31