TABLE 4 – APPROXIMATE INSULATION FOR HOT AND COLD SURFACES<br />
42<br />
COLD SURFACES HOT SURFACES<br />
Chiller<br />
Model<br />
Evap. Heads<br />
&<br />
End Sheets<br />
(Sq. Feet)<br />
Refrig. Outlet<br />
Box &<br />
Pump<br />
(Sq. Feet)<br />
Refrig. Suction &<br />
Discharge lines<br />
(Tubular insul.)<br />
(Dia. inch/lin feet)<br />
Evap.<br />
Shell<br />
(optional)<br />
(Sq. Feet)<br />
Upper Shell<br />
(Sq. Feet)<br />
Evap.<br />
Heads<br />
(Sq. Feet)<br />
1A1 16 16 2"/11', 4"/4' 52 70 2<br />
1A2 16 16 2"/12', 4"/3' 63 70 2<br />
2A3 16 16 2"/12', 4"/3' 73 81 2<br />
2A4 16 16 2"/13', 4"/3' 84 93 2<br />
2B1 19 17 2"/9', 2-1/2"/4', 4"/4' 84 95 3<br />
3B2 19 17 2"/10', 2-1/2"/4', 4"/4' 96 110 3<br />
3B3 19 17 2"/11', 2-1/2"/4', 4"/4' 108 125 3<br />
4B4 19 18 2"/12', 2-1/2"/4', 4"/4' 120 136 3<br />
4C1 26 18 2-1/2"/11', 3"/4', 4"/6' 111 132 4<br />
5C2 26 18 2"/12', 3"/4', 4"/6' 125 148 4<br />
5C3 26 18 2-1/2"/13', 3"/4', 4"/6' 139 165 4<br />
6C4 26 18 2-1/2"/14', 3"/4', 4"/6' 156 185 4<br />
7D1 39 31 3"/17', 4"/6' 156 180 7<br />
7D2 39 31 3"/18', 4"/6' 173 200 7<br />
8D3 39 31 3"/19', 4"/6' 194 225 7<br />
8E1 55 43 3"/22', 4"/8' 194 225 8<br />
9E2 55 43 3"/24', 4"/8' 218 255 8<br />
10E3 55 43 3"/24' 242 285 8<br />
12F1 67 44 3"/21' 242 290 10<br />
13F2 67 44 3"/23' 268 320 10<br />
14F3 67 44 3"/24' 295 355 10<br />
NOTES:<br />
1. Evaporator shell insulation is only required if evaporator shell surface sweats.<br />
2. Cold surface insulation on the refrigerant outlet box, refrigerant pump, refrigerant pump suction and discharge lines may be purchased<br />
as an extra option from the factory.<br />