20.03.2013 Views

OPERATOR'S MANUAL BIOPROtect II JR Vent to ... - Baker Company

OPERATOR'S MANUAL BIOPROtect II JR Vent to ... - Baker Company

OPERATOR'S MANUAL BIOPROtect II JR Vent to ... - Baker Company

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

The Airflow Balance<br />

Warning!<br />

This procedure should be performed by qualified technicians only.<br />

The airflow balance which is set at the fac<strong>to</strong>ry provides your unit with the air volume and velocity control<br />

<strong>to</strong> minimize leakage or airborne contamination either in or out of the work area.<br />

In order <strong>to</strong> duplicate as closely as possible the airflow characteristics described in the original fac<strong>to</strong>ry test<br />

report, please follow these steps:<br />

1. Make certain that the front door and viewscreen are closed and secured so as <strong>to</strong> make an 8” x 42”<br />

horizontal access opening.<br />

2. Using a DIM (Direct Intake Measurement) measure the flow rate in<strong>to</strong> the front access opening. Take at<br />

least five (5) consecutive readings. Average the readings and divide by 2.3 square feet (area of the front<br />

access opening). Acceptable range of the average shall be 100-110 FPM.<br />

3. Using a hot wire anemometer mounted on a ring stand within the work area, take readings with the<br />

anemometer probe set 6” below the diffuser. The location of these readings should be the same as shown in<br />

the fac<strong>to</strong>ry test report. The average of these velocity readings must be in the range between 50 and 70 FPM.<br />

4. After you have compared your figures with those originally taken at the fac<strong>to</strong>ry, make whatever<br />

adjustments are necessary. Use the mo<strong>to</strong>r speed control and the exhaust damper <strong>to</strong> bring the intake and<br />

downflow average values within the specifications.<br />

5. As the HEPA filters load up with particulates, airflow will be maintained au<strong>to</strong>matically <strong>to</strong> some extent.<br />

When the air flow is diminished you will have <strong>to</strong> increase the mo<strong>to</strong>r speed <strong>to</strong> maintain the specified intake<br />

and downflow velocity averages. This is done via the speed controller located in the light canopy.<br />

Warning!<br />

When the light canopy is lowered, some electrical parts are exposed. Do not perform this work unless<br />

you are a trained electrician or electronic technician.<br />

!!!!Note that terminals M1 & M2 as well as L1 & L2 are high Voltage.!!!!<br />

On the speed controller, turn the potentiometer clockwise until you have the desired airflow. Use a<br />

voltmeter <strong>to</strong> check the voltage across terminals M1 & M2. This is the voltage out <strong>to</strong> the mo<strong>to</strong>r. If the airflow<br />

cannot be maintained, it will necessary <strong>to</strong> replace the HEPA filters.<br />

(See “Procedure for HEPA Filter Replacement” later in this section.).<br />

http://solid/prereleased/prereleased/STAN. PRODUCT/313/DOCS/313D000.doc<br />

Page 18 of 59

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!