Units equipped with fixed VTs<br />
To have an easier access inside<br />
the cubicle, remove the bottom<br />
sheet of the circuit-breaker<br />
compartment and the barriers<br />
between phases.<br />
30 - 07897542EN indice: D0<br />
Mobile part extraction<br />
- Close the earthing switch (see page 78).<br />
- Remove the 2 fixing bolts by using the<br />
operating crank.<br />
- Open the access door.<br />
- Disconnect the connection bar of each VT<br />
by unscrewing the nut.<br />
- Open the circuit-breaker compartment<br />
door.<br />
- Remove the bottom plate of the<br />
circuit-breaker compartment by unscrewing<br />
the 4 fixing bolts.<br />
- Disconnect the LV connector of the VT<br />
secondaries.<br />
- Remove the 2 bolts.<br />
- Remove the 5 nuts fixing and the<br />
crosspiece.<br />
- Remove the VT assembly, by running it on<br />
its wheels.<br />
- Remove the barriers between phases<br />
following the sequence indicated in the<br />
figure.<br />
- Close again the circuit-breaker’s and VTs’<br />
compartment doors.<br />