Units equipped with fixed VTs<br />

To have an easier access inside<br />

the cubicle, remove the bottom<br />

sheet of the circuit-breaker<br />

compartment and the barriers<br />

between phases.<br />

30 - 07897542EN indice: D0<br />

Mobile part extraction<br />

- Close the earthing switch (see page 78).<br />

- Remove the 2 fixing bolts by using the<br />

operating crank.<br />

- Open the access door.<br />

- Disconnect the connection bar of each VT<br />

by unscrewing the nut.<br />

- Open the circuit-breaker compartment<br />

door.<br />

- Remove the bottom plate of the<br />

circuit-breaker compartment by unscrewing<br />

the 4 fixing bolts.<br />

- Disconnect the LV connector of the VT<br />

secondaries.<br />

- Remove the 2 bolts.<br />

- Remove the 5 nuts fixing and the<br />

crosspiece.<br />

- Remove the VT assembly, by running it on<br />

its wheels.<br />

- Remove the barriers between phases<br />

following the sequence indicated in the<br />

figure.<br />

- Close again the circuit-breaker’s and VTs’<br />

compartment doors.<br />