Close the earthing switch<br />

78 - 07897542EN indice: D0<br />

Tests on <strong>site</strong><br />

Push the pushbutton of the earthing switch<br />

electromechanical lock. If the cubicle is not<br />

equipped with this option, go directly to the<br />

following sequence.<br />

Insert the crank into hole 5 and turn it<br />

clockwise until the earthing switch position<br />

indicator reads “on”.<br />

The earthing switch is in closed position.<br />

The MV cables are short-circuited and<br />

earthed. The selector in this position<br />

prevents the insertion of the circuit-breaker.<br />

Set selector 4 to .<br />

This operation requires first to pull outward<br />

the selector and then to turn it.<br />

Turn selector 4 clockwise to position I.<br />

The symbols marked on the yellow front<br />

cover summarise the above-mentioned<br />

procedure.<br />

For more protection, it is possible to prevent<br />

the insertion of the circuit-breaker by setting<br />

the selector P as shown in the following<br />

drawing.<br />