1 Operating Instructions for the Pellet Boiler<br />

1.1 Delivery<br />

The KUENZEL Pellet Boiler is sealed in environmentally–friendly PE foil and is delivered on disposable<br />

pallets with an enclosed control panel and ventilator.<br />

1.2 Accessories<br />

Enclosed with the pellet <strong>boiler</strong> are:<br />

1 guarantee card<br />

1 cleaning brush<br />

15 kg <strong>pellets</strong><br />

1.3 Installation Directions<br />

This pellet <strong>boiler</strong> has been approved for operation with an open or closed heating system with an allowed<br />

operational pressure of a maximum 3 bar and a maximum flow temperature of 95◦ C.<br />

The pellet <strong>boiler</strong> must not be operated without the <strong>boiler</strong> back end protection. The function of the <strong>boiler</strong><br />

back–end protection should be supervised. With systems without a buffer storage, a 4–way mixer is<br />

sufficient as the <strong>boiler</strong> back–end protection.<br />

This pellet <strong>boiler</strong> must only be operated with fuel according to the German norm BImSchV figure 5a<br />

(using wooden <strong>pellets</strong> made of natural untreated wood). (This <strong>boiler</strong> corresponds to the German official<br />

acts for operating <strong>boiler</strong>s as well as to the DIN EN 303–5). (DIN stands for Deutsche Industrie Norm<br />

which means the German Industry Norm)<br />

Only <strong>pellets</strong> with a diameter of 6mm or 8mm are permitted. The <strong>pellets</strong> must correspond to the standard<br />

of the DIN Plus or of the PVA (Pellets Association Austria). Other fuels, especially <strong>pellets</strong> which contain<br />

recycled material, must not be used.<br />

Please be aware that the DIN 51731 <strong>pellets</strong> can have a higher proportion of ash and a minor non–<br />

abrasiveness than the PVA or DIN Plus <strong>pellets</strong>. The minor non–abrasiveness can cause a considerably<br />

high proportion of dust which may lead to failure of the screw conveyor. DIN 51731 <strong>pellets</strong> are, as a rule,<br />

not suitable for operation in the pellet <strong>boiler</strong> due to their bad material properties.<br />

The details of the cleaning schedule refers to the PVA <strong>pellets</strong>. When other <strong>pellets</strong> are used, a more<br />

frequent cleaning might be required, as there is a danger of a heavy slag build–up in the burner.<br />

In the interests of operation safety, it is not advisable to put in other fuels than DIN–Plus or PVA–<br />

Standard <strong>pellets</strong>!<br />

Do not fill the <strong>boiler</strong> with shavings or dust.<br />

–Danger of explosion–<br />

All KUENZEL products are subject to technical alterations. KUENZEL assumes no liability for functional<br />

problems due to using component parts which are no KUENZEL products. This refers especially to<br />

control devices of other makes. KUENZEL assumes no liability either in case of operating problems due<br />

to on–site conditions like the hydraulic system, exhaust gas system or external conveyor technique.<br />