Abbildung 3: Flange screws in pellet bin<br />

In order to carry the main body of the <strong>boiler</strong>, there are two points of attachment on the right and left sides<br />

of the <strong>boiler</strong> into which 1“ pipe ends can be screwed.<br />

Now, the body of the <strong>boiler</strong> is able to be carried.<br />

1.9 Chimney <strong>Co</strong>nnection<br />

The KUENZEL pellet <strong>boiler</strong> is equipped with an exhaust gas ventilator. The ventilator can be fitted with<br />

the exhaust gas escape which can point optionally to the right, to the left or in an upward direction. An<br />

exhaust gas escape pointing downwards is not permissable.<br />

The exhaust pipe to the chimney should be short, without any extra bends if possible and fixed in an<br />

upward direction. When inserting it into the chimney, it should be rounded off at the top and fitted into a<br />

position which allows the draught current to flow through well.<br />

For any important information regarding the chimney calculations please refer to the technical data in<br />

chapter ?? auf Seite ??. To use a chimney which has a smaller diameter than the smoke ducts is not<br />

permissable.<br />

Caution: Please be aware that with the low exhaust temperatures occuring constantly whilst in operation,<br />

a damp–resistant fireplace (heat–flow number and resistance group I of the type DIN 18160/T1) may be<br />

required.<br />

If the <strong>boiler</strong> has to be connected to an already existing chimney, the dimensions of the chimney must<br />

be calculated / a chimney report must be done beforehand. The agreement of your local chimney sweep<br />

service must be obtained before installation.<br />

Due to the ventilator, disruptive noises can occur at the chimney. For this reason, we recommend that the<br />

connection should be made with a flexible exhaust gas pipe input into the chimney.<br />

Make sure that the exhaust gas pipe has been tested to be free of leaks, as otherwise exhaust fumes could<br />

escape into the <strong>boiler</strong> room. This applies especially to the cleaning openings at the bends in the pipe.<br />

1.10 Heating <strong>Co</strong>nnection<br />

In order to avoid operational disruptions, we recommend to you that the heating connection should be<br />

formed according to one of the published KUENZEL system packages. For this, please note chapter3<br />