3 UPS 0.6 KVA<br />
Makes Recommended:<br />
APC / LIEBERT / TVSE / VINITEC / WIPRO<br />
Type: Line Interactive<br />
Rating: Min. 600 VA<br />
Input <strong>Supply</strong>:180 V to 275 V AC<br />
Nominal Output:<br />
i) On Grid –190 V to 240 V AC<br />
ii) On Battery- 230V AC + 5%,<br />
50 + 0.5 Hz<br />
Battery:<br />
Back up time – Min. 10 minutes on 450 VA<br />
continuous load<br />
Type – SMF<br />
Recharge time – < than 6 hours<br />
Makes – Hitachi/ Global Yuasa/ CSB/<br />
Panasonic/ Exide,<br />
Pls. specify<br />
Transfer time:<br />
< 5 ms without losing data<br />
Built in AVR- Required<br />
Protection: Overload, Short circuit, Spike &<br />
Surge<br />
Indications: Mains ON, Battery ON,<br />
Overload<br />
Audio Alarms: Low battery, Battery ON,<br />
Overload<br />
Communications:<br />
Hardware:<br />
RS 232-C Serial port or USB port with<br />
Interface cable -3 feet length,<br />
S<strong>of</strong>tware:<br />
Required for health monitoring <strong>of</strong> battery<br />
<strong>and</strong> Power Mgmt. System<br />
O/P Sockets – Min. 3 nos.,<br />
Each 6A, 3 pins (Min. 2 nos. sockets shall be<br />
wired for UPS O/P)<br />
Power Cables - For all the O/P sockets<br />
each min. 4 ft. long IN CASE the UPS has<br />
BN 55 etc. type O/P Power receptacles for<br />
feeding AC power to CPU box, Monitor etc.<br />
Documentation:<br />
Operation Manual<br />
Operation Training:<br />
Shall be provided to the Users at <strong>GAIL</strong>’s<br />
Offices<br />