3 Technical data<br />
3.1 Standards<br />
UPS 20kVA 30kVA 40kVA<br />
Safety IEC62040-1-1:2004,EN62040-1-1:2003 and EN60950-1:2001<br />
EMC IEC62040-2:2005 and EN62040-2:2006<br />
<strong>Product</strong> IEC62040-3:1999 and EN62040-3:2001<br />
3.2 Environment<br />
UPS 20kVA 30kVA 40kVA<br />
Ambient 0 to +40℃(UPS), 15 to +25℃(battery cabinet(s))<br />
Relative humidity 20% to 90%, no condensation allowed<br />
Altitude derating coefficient See user operations section for more detail information<br />
Vibration IEC68-2-6; max.0.3mm(2 to 9Hz), max.1m/s2(9 to 200Hz) sinusoidal<br />
3.3 Dimensional drawings<br />
UPS 20kVA 30kVA 40kVA<br />
Width 420mm 470mm 470mm<br />
Depth 643mm 710mm 710mm<br />
Height 956mm 1150mm 1150mm<br />
N.W(Kg) 82 110 114<br />
G.W(Kg) 122 160 164<br />
9