Notice!<br />

The following label must be displayed on all switching devices installed in the same<br />

electrical system as the UPS, even when these are located at a distance from the area<br />

in which it is located (according to European standard EN 62040-1-1).<br />

Warning!<br />

ENSURE THAT THE UNINTERRUPTIBLE POWER SYSTEM IS ISOLATED BEFORE<br />

WORKING ON THIS CIRCUIT.<br />

5.4 Connecting the external battery<br />

Before connecting the external battery, please read the notice and warning label<br />

on the UPS.<br />

Warning!<br />

In the event of malfunction, the battery cabinet chassis or battery cabinet frames may<br />

become live!<br />

Warning!<br />

Special care should be taken when working with the battery cabinet associated with<br />

the <strong>Eaton</strong> E <strong>Series</strong> <strong>DX</strong> 20 - 40 kVA. When the battery cabinet is connected the overall<br />

voltage exceeds 400V. It is very important to ensure that the batteries are installed<br />

separately, in a dedicated battery cabinet.<br />