4.3 Planning before installation<br />
The equipment must be installed in upright position. The equipment requires space to front<br />
and back to enable cooling airflow. Service and maintenance require more than 40cm clear-<br />
ance on right hand side. All cooling air enters at front and exits at unit rear. The required<br />
minimum clearance from unit rear to an obstruction is 50cm. Because the service and user<br />
access is in the front there should be reserved enough space (min 60cm).<br />
Preparation for installation.<br />
1. Avoid extremes of ambient temperature; excessive dust, moisture or vibration; flammable<br />
gases; and corrosive or explosive atmospheres.<br />
2.Altitude for normal UPS function should not exceed 1000m.<br />
3.The battery cabinet should work within a temperature range from15℃ to 25℃.<br />
4.The maximum ambient temperature for normal UPS performance should not exceed 40℃.<br />