7.UPS is now in the maintenance bypass mode,see below:<br />

Transfer UPS from maintenance bypass mode to normal mode:<br />

1.The normal start position should be following:<br />

2.Turn ON the Bypass Input switch and N switch<br />

When the LED of bypass turns green,the UPS enters into bypass mode.<br />

3.Turn the Maintenance switch to “UPS” side.<br />

19