7.UPS is now in the maintenance bypass mode,see below:<br />
Transfer UPS from maintenance bypass mode to normal mode:<br />
1.The normal start position should be following:<br />
2.Turn ON the Bypass Input switch and N switch<br />
When the LED of bypass turns green,the UPS enters into bypass mode.<br />
3.Turn the Maintenance switch to “UPS” side.<br />
19