Software "Venetian blind, input 20BD11"<br />
Object table<br />
4.2.3 Object table<br />
Number of communication objects: 28<br />
(max. object number 55 - gaps in between)<br />
Number of addresses (max): 254<br />
Number of assignments (max): 255<br />
Dynamic table management<br />
Yes<br />
Maximum table length 255<br />
4.2.3.1 Extension input objects<br />
Function:<br />
Switching<br />
Object<br />
h 10,<br />
11,<br />
12<br />
Function<br />
Switching object X.1<br />
Name<br />
Input 1 ... 3 1<br />
Type<br />
1-bit<br />
DPT<br />
1.<strong>00</strong>1<br />
Flag<br />
C, W, T 2<br />
Description<br />
1-bit object for the transmission of switching telegrams (ON, OFF)<br />
(first switching object)<br />
Function:<br />
Switching<br />
Object<br />
h 14,<br />
15,<br />
16<br />
Function<br />
Switching object X.2<br />
Name<br />
Input 1 ... 3 1<br />
Type<br />
1-bit<br />
DPT<br />
1.<strong>00</strong>1<br />
Flag<br />
C, W, T 2<br />
Description<br />
1-bit object for the transmission of switching telegrams (ON, OFF)<br />
(second switching object)<br />
Function:<br />
Dimming<br />
Object<br />
h 10,<br />
11,<br />
12<br />
Function<br />
Switching<br />
Name<br />
Input 1 ... 3 1<br />
Type<br />
1-bit<br />
DPT<br />
1.<strong>00</strong>1<br />
Flag<br />
C, W, T 2<br />
Description<br />
1-bit object for the transmission of switching telegrams (ON, OFF) for the<br />
dimming function.<br />
Function:<br />
Dimming<br />
Object<br />
h 14,<br />
15,<br />
16<br />
Function<br />
Dimming<br />
Name<br />
Input 1 ... 3 1<br />
Type<br />
4-bit<br />
DPT<br />
3.<strong>00</strong>7<br />
Flag<br />
C, W, T 2<br />
Description 4-bit object for change of relative brightness between 0 and 1<strong>00</strong> %.<br />
1: The objects for inputs 1 and 2 are not available when inputs have an internal effect on the<br />
Venetian blind output.<br />
2: Each communication object can be read out. For reading, the R-flag must be set.<br />