Software "Venetian blind, input 20BD11"<br />

Object table<br />

Function:<br />

Sun protection function<br />

Object<br />

h 47<br />

Function<br />

Sunshine slat position offset<br />

Name<br />

Output 1<br />

Type<br />

1 byte<br />

DPT<br />

6.<strong>00</strong>1<br />

Flag<br />

C, S, - 1<br />

Description<br />

1-byte object for presetting a slat position angle (- 1<strong>00</strong> % … +1<strong>00</strong> % / smaller<br />

or larger position angles are treated as + or – 1<strong>00</strong> %) for 'manual'<br />

readjustment of the slat position during active sun protection.<br />

Function:<br />

Sun protection function – automatic heating/cooling<br />

Object<br />

h 48<br />

Function<br />

Heating/cooling presence<br />

Name<br />

Output 1<br />

Type<br />

1-bit<br />

DPT<br />

1.018<br />

Flag<br />

C, S, - 1<br />

Description<br />

1 -bit object for activation of the presence mode during<br />

automatic heating/cooling. The polarity can be configured. This object is<br />

generally linked with presence detectors.<br />

Function:<br />

Sun protection function – automatic heating/cooling<br />

Object<br />

h 49<br />

Function<br />

Heating/cooling switchover<br />

Name<br />

Output 1<br />

Type<br />

1-bit<br />

DPT<br />

1.1<strong>00</strong><br />

Flag<br />

C, S, - 1<br />

Description<br />

1-bit object for switching over between heating and cooling operation during<br />

automatic heating/cooling. The polarity can be configured. This object is<br />

generally linked with room temperature controllers<br />

(object "heating/cooling switchover").<br />

Function:<br />

Position feedback<br />

Object<br />

h 50<br />

Function<br />

Position feedback 2<br />

Name<br />

Output 1<br />

Type<br />

1 byte<br />

DPT<br />

5.<strong>00</strong>1<br />

Flag<br />

C, -, T, R 3<br />

Description<br />

1-byte object for position feedback of the Venetian blind or roller shutter height<br />

or louver position (0…255).<br />

Function:<br />

Position feedback<br />

Object<br />

h 51<br />

Function<br />

Slat position feedback<br />

Name<br />

Output 1<br />

Type<br />

1 byte<br />

DPT<br />

5.<strong>00</strong>1<br />

Flag<br />

C, -, T, R 3<br />

Description<br />

1-byte object for position feedback of the slat position (0…255) if one shutter<br />

is controlled.<br />

1: For reading, the R-flag must be set. The last value written to the object via the bus will be<br />

read.<br />

2: The object designation varies with the type of blind (Venetian blind, roller shutter / awning,<br />

venting louver).<br />

3: The communication flags are set automatically depending on the configuration. "T" flag for<br />

active signalling object; "R" flat for passive status object.<br />

<strong>Order</strong>-<strong>No</strong>. <strong>2165</strong> <strong>00</strong><br />