Software "Venetian blind, input 20BD11"<br />
Functional description<br />
- If a falling flank is detected within the slat adjustment time, the input transmits an additional<br />
short time telegram. This function is used for adjusting the slats of a blind. The function<br />
permits stopping the slats in any position during their rotation.<br />
The "slat adjusting time" should be chosen as required by the drive for a complete rotation<br />
of the slats. If the "slat adjusting time" is selected longer than the complete running time of<br />
the drive, a pushbutton function is possible as well. This means that the drive is active only<br />
when a button connected to the input is kept depressed.<br />
- If the button is kept depressed longer than T2, the input transmits no further telegram. The<br />
drive remains on until the end position is reached.<br />
Figure 8: Operation concept "long – short"<br />
Operation concept "long – short":<br />
In the operation concept "long – short", the input shows the following behaviour:<br />
- Immediately on pressing the button, the input transmits a long time telegram. The drive<br />
begins to move and time T1 ("slat adjusting time") is started.<br />
- If a falling flank is detected within the slat adjustment time, the input transmits a short time<br />
telegram. This function is used for adjusting the slats of a blind. The function permits<br />
stopping the slats in any position during their rotation.<br />
The "slat adjusting time" should be chosen as required by the drive for a complete rotation<br />
of the slats. If the "slat adjusting time" is selected longer than the complete running time of<br />
the drive, a pushbutton function is possible as well. This means that the drive is active only<br />
when a button connected to the input is kept depressed.<br />
- If the button is kept depressed longer than T1, the input transmits no further telegram. The<br />
drive remains on until the end position is reached.<br />
Flank evaluation<br />
The parameter "Command on rising flank" on the parameter page "Ix - General" (x = 1, 2, 3)<br />
specifies the direction of movement of the short time or long time telegram. In the "TOGGLE"<br />
setting (single-surface operation) the input switches the direction of the short and long time<br />
telegram each time there is a new signal. Several short time telegrams in succession have the<br />
same direction.<br />
i If the <strong>actuator</strong> is to be controlled from several locations, a faultless single-surface actuation<br />
requires that the all long time objects of the sensor devices are interlinked. A sensor device<br />
would otherwise not be able to detect that the <strong>actuator</strong> has been addressed from another<br />
sensor, in which case it would have to be actuated twice during the next use in order to<br />
produce the desired reaction.<br />
Response to bus voltage return<br />
After a device reset (bus voltage return or ETS programming operation), the communication<br />
object "Long time operation" of the input can be initialised. For this, the "Behaviour on bus<br />
voltage return" parameter should be configured to the required reaction. In the settings "Up" or<br />
"Down", telegrams are transmitted actively to the bus.<br />
If, in the ETS, a delay is set for the extension inputs after bus voltage return, the device only<br />
transmits the telegrams when the delay has elapsed.<br />
After a device reset, the "Short time operation" object is always initialised with "0".<br />