In Figure 5 an Option <strong>Power</strong> Supply (OPS) and a Remote Status Panel (RAS) have been added to the CANbus.<br />

The Option <strong>Power</strong> Supply contains an isolated CANbus repeater so the CANbus in the OPS/RAS loop is considered<br />

to have originated at that point only to the RAS panel. The isolated output of the OPS is pre-configured with<br />

a terminator on the included terminal block.<br />

Notes For Figure 5<br />

1. CANbus cable for providing power and signals for the communication option is installed in the UPS and is<br />

coiled up in the option section.<br />

2. Connect the CANbus cable to P999 of the option located in Location 4. See Section 8 if option D, Option<br />

<strong>Power</strong> Supply is to be installed.<br />

3. Always insure that the CANbus cable originating from the power supply PWA gets connected to P999 of the<br />

bottom-most option of the group in Locations 1 through 5. (Option in Location 6 is not considered as part of<br />

this group.)<br />

4. Additional options can be cabled together using one of the CANbus jumper cables. The jumpers plug into<br />

connector P966 of the lower option and into connector P999 of the next option above.<br />

5. All user option connecting cables are to be provided by others and are to be 16 gauge 300V Min. tinned<br />

copper stranded wire. All option connections are made in the option section. Customer wires route through<br />

option plate.<br />

6. Option connection cables must be run in separate conduit from CANbus power cables.<br />

7. Use short CANbus jumper (PN 77-814000-04) to daisy chain options.<br />

8. Use long CANbus jumper (PN 77-814000-03) to connect P966 at Location 3 and 4.<br />

10 General information concerning 4 x 7 Option Cards