03.01.2014 Views

SL-24533.book(SL-24533 FC.fm) - Emerson Network Power

SL-24533.book(SL-24533 FC.fm) - Emerson Network Power

SL-24533.book(SL-24533 FC.fm) - Emerson Network Power

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

7.0 OPEN COMMS – DISCRETE INPUT OPTION (OC-DI) (INPUT CONTACT<br />

ISOLATOR)<br />

7.1 Introduction<br />

This Option will allow the user to bring up to 8 outside signals into the Npower UPS. A customer contact closure<br />

(no voltage) is needed to activate the relay. The UPS can then be programmed to alarm on receipt of one or more<br />

of these signals and to display the user settable name of the signal source. In addition the signals can be set to<br />

trigger NO or NC relays on the Open Comms Discrete Output Option (OC-DO), Section 6, if the system is configured<br />

with this option.<br />

7.2 Installation<br />

Physically install the OC-DI board in the Npower UPS in accordance with the instructions in Section 4 of this<br />

manual. This option can be installed in Locations 1, 2, 3 or 4. Once installed, the OC-DI board needs to be connected<br />

to the CANbus. If it is the first option installed, install in location 4 (See Figure 3), and utilize the system<br />

CANbus cable that is coiled in the center of the option area. If another option has been previously installed and<br />

connected to the system CANbus cable, use either the short (77-814000-03) or the long (77-814000-04) jumper<br />

cable as required. Connect this system harness to the P966 connector on the left side of the OC-DI board.<br />

Bring up to 8 pairs of wires (one pair for each customer signal, up to 16 wires total) to the Npower UPS from the<br />

customers Normally Open or Normally Closed sources. These wires should be delivered to the Npower in appropriately<br />

sized conduit. The wires connect to the UPS through the cable landing area in the upper or lower front of<br />

the UPS (Figure 3). Wires should be routed down the right side of the option area and then at a 90 degree angle<br />

to the option board. Next, connect the wire pairs to TB1.<br />

All user connecting cables are to be provided by others and are to be 16 gauge 300 V Min. tinned copper stranded<br />

wire. All option connections are made in the option section. Customer wires route through option plate.<br />

32 Open COMMS – Discrete Input Option (OC-DI) (Input Contact Isolator)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!