(IV-7-3) General Safety
(IV-7-3) General Safety
(IV-7-3) General Safety
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Rules <strong>IV</strong> Industrial Services<br />
Part 7 Offshore Substations<br />
Chapter 3 <strong>General</strong> <strong>Safety</strong><br />
Section 7<br />
Passive Fire Protection<br />
Section 7<br />
Passive Fire Protection<br />
A Materials and Definition of Spaces ............................................................................. 7-1<br />
B Ventilation and Fire Dampers ..................................................................................... 7-6<br />
A<br />
Materials and Definition of Spaces<br />
A.1 Scope<br />
Passive fire protection shall ensure that relevant structures, piping and equipment components have adequate<br />
fire resistance with regard to load bearing properties, integrity and insulation properties during a<br />
dimensioning fire, and contribute in reducing the consequences in general.<br />
Fire divisions shall ensure that a dimensioning fire and explosion does not escalate into surrounding areas.<br />
Passive fire protection shall prevent or mitigate serious consequences from fire also to protect personnel<br />
(heat and smoke) and make escape or evacuation possible.<br />
A.2 Definitions of spaces<br />
A.2.1<br />
Control stations<br />
Spaces which contain the following equipment are considered as Control Stations:<br />
• operational control systems<br />
• radio and telephone systems including emergency communication<br />
• fire detection and fire control systems<br />
• emergency source of power<br />
• fire extinguishing systems serving various locations<br />
A.2.2<br />
Corridors<br />
Corridors are spaces which serve the purpose of connecting other areas in order to provide carriage of<br />
personnel.<br />
A.2.3<br />
Accommodation spaces<br />
Accommodation spaces are those used as public spaces, corridors, lavatories, cabins, offices, hospitals,<br />
cinemas, recreational rooms, pantries containing no cooking appliances and similar spaces.<br />
Public spaces are those portions of the accommodation which are used for halls, dining rooms, lounges<br />
and similar permanently enclosed spaces.<br />
A.2.4<br />
Stairways<br />
Stairways are internal stairways, lifts and escalators (other than those wholly contained within the machinery<br />
spaces) and enclosures thereto.<br />
In this connection a stairway, which is enclosed only at one level, shall be regarded as part of the space<br />
from which it is not separated by a fire door.<br />
A.2.5<br />
Service spaces (low risk)<br />
Service spaces (low risk) are lockers, laundries, store rooms and working spaces, in which no flammable<br />
materials are stored.<br />
Edition 2013 Germanischer Lloyd Page 7–1