01.03.2014 Views

(IV-7-3) General Safety

(IV-7-3) General Safety

(IV-7-3) General Safety

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Rules <strong>IV</strong> Industrial Services<br />

Part 7 Offshore Substations<br />

Chapter 3 <strong>General</strong> <strong>Safety</strong><br />

Section 7<br />

Passive Fire Protection<br />

Section 7<br />

Passive Fire Protection<br />

A Materials and Definition of Spaces ............................................................................. 7-1<br />

B Ventilation and Fire Dampers ..................................................................................... 7-6<br />

A<br />

Materials and Definition of Spaces<br />

A.1 Scope<br />

Passive fire protection shall ensure that relevant structures, piping and equipment components have adequate<br />

fire resistance with regard to load bearing properties, integrity and insulation properties during a<br />

dimensioning fire, and contribute in reducing the consequences in general.<br />

Fire divisions shall ensure that a dimensioning fire and explosion does not escalate into surrounding areas.<br />

Passive fire protection shall prevent or mitigate serious consequences from fire also to protect personnel<br />

(heat and smoke) and make escape or evacuation possible.<br />

A.2 Definitions of spaces<br />

A.2.1<br />

Control stations<br />

Spaces which contain the following equipment are considered as Control Stations:<br />

• operational control systems<br />

• radio and telephone systems including emergency communication<br />

• fire detection and fire control systems<br />

• emergency source of power<br />

• fire extinguishing systems serving various locations<br />

A.2.2<br />

Corridors<br />

Corridors are spaces which serve the purpose of connecting other areas in order to provide carriage of<br />

personnel.<br />

A.2.3<br />

Accommodation spaces<br />

Accommodation spaces are those used as public spaces, corridors, lavatories, cabins, offices, hospitals,<br />

cinemas, recreational rooms, pantries containing no cooking appliances and similar spaces.<br />

Public spaces are those portions of the accommodation which are used for halls, dining rooms, lounges<br />

and similar permanently enclosed spaces.<br />

A.2.4<br />

Stairways<br />

Stairways are internal stairways, lifts and escalators (other than those wholly contained within the machinery<br />

spaces) and enclosures thereto.<br />

In this connection a stairway, which is enclosed only at one level, shall be regarded as part of the space<br />

from which it is not separated by a fire door.<br />

A.2.5<br />

Service spaces (low risk)<br />

Service spaces (low risk) are lockers, laundries, store rooms and working spaces, in which no flammable<br />

materials are stored.<br />

Edition 2013 Germanischer Lloyd Page 7–1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!