Part 7 Offshore Substations<br />
Chapter 3 <strong>General</strong> <strong>Safety</strong><br />
Section 7<br />
Passive Fire Protection<br />
closed, shall provide resistance to fire as well as to the passage of smoke and flames, as far as practicable,<br />
equivalent to that of the bulkheads in which the doors are situated.<br />
Such doors and door frames shall be constructed of steel or other equivalent material. Doors in "A" class<br />
divisions must be capable of being opened and closed from each side of the bulkhead by one person<br />
only.<br />
A.5.2 Intersections and penetrations<br />
In approving fire protection details, GL will have regard to the risk of heat transmission at intersections<br />
and thermal points of required thermal barriers.<br />
Where "A" class divisions are pierced for the passage of electric cables, pipes, trunks, ducts, etc., or for<br />
girders, beams or other structures, arrangements shall be made to ensure that the fire resistance is not<br />
impaired. Penetrations to be of approved type.<br />
If a space is divided with a deck or bulkhead of “A” class standard having insulation of different values,<br />
the insulation with the higher value should continue on the deck or bulkhead with the insulation of the<br />
lesser value for a distance of at least 450 mm.<br />
A.5.3 Windows<br />
GL permits windows outside hazardous areas to be of opening type.<br />
A.5.4 Corridors<br />
All bulkheads required to be "B" class divisions shall extend from deck to deck and to the deckhouse side<br />
or other boundaries, unless continuous "B" class ceilings or linings are fitted on both sides of the bulkhead,<br />
in which case the bulkhead may terminate at the continuous ceiling or lining.<br />
In corridor bulkheads, ventilation openings may be permitted only in and under the doors of cabins, public<br />
spaces, offices and sanitary spaces. The openings shall be provided only in the lower half of the door.<br />
Where such an opening is in or under a door, the total net area of any such opening or openings shall not<br />
exceed 0.05 m 2 . When such an opening is cut in a door it shall be fitted with a grille made of noncombustible<br />
material. Such openings shall not be provided in a door in a division forming a stairway closure.<br />
A.5.5 Stairs<br />
Stairs shall be constructed of steel or equivalent material.<br />
A.5.6 Stairways and lifts<br />
Stairways which penetrate only a single deck shall be protected at least at one level by "A" or "B" Class<br />
divisions and self-closing doors so as to limit the rapid spread of fire from one deck to another.<br />
Stairways and lift shafts which penetrate more than a single deck shall be surrounded by "A" class divisions<br />
and protected by self-closing doors at all levels.<br />
Self-closing doors shall not be fitted with hold-back hooks. However, hold-back arrangements incorporating<br />
remote release fittings of the fail-safe type may be utilized.<br />
Personnel lift trunks shall be protected by "A" class divisions.<br />
A.5.7 Air spaces<br />
Air spaces enclosed behind ceilings, paneling’s or linings shall be divided horizontally by close fitting<br />
draught stops spaced not more than 14 meters apart.<br />
In the vertical direction, such enclosed air spaces, including behind linings of stairways, trunks, etc.<br />
should be closed at each deck.<br />
A.5.8 Insulation<br />
Except for insulation in refrigerated compartments, insulation material, pipe and vent duct lagging, ceilings,<br />
linings and bulkheads shall be of non-combustible material. Insulation of pipe fittings for cold ser-<br />
Edition 2013 Germanischer Lloyd Page 7–5