Rules <strong>IV</strong> Industrial Services<br />

Part 7 Offshore Technology<br />

Chapter 3 <strong>General</strong> <strong>Safety</strong><br />

Section 8<br />

Active Fire Protection<br />

G.2.6.3 The mechanical ventilation of the protected space is to be stopped automatically before the<br />

discharge of the extinguishing gas.<br />

G.2.6.4 Audible and visual alarms shall be provided in the protected space and additional visual<br />

alarms at each access to the space.<br />

G.2.6.5 The alarm shall be actuated automatically by opening of the release station door. For installations<br />

with a design concentration in excess of the NOAEL, see G.2.1.3, means shall be provided to safeguard<br />

that the discharge of extinguishing gas is not possible before the alarm has been actuated for a<br />

period of time necessary to evacuate the space but not less than 20 s.<br />

G.2.6.6 Audible alarms shall be of horn or siren sound and be clearly distinguishable from other audible<br />

signals.<br />

G.2.6.7<br />

power.<br />

Electrical alarm systems shall have power supply from the main and emergency source of<br />

G.2.6.8 For the use of electrical alarm systems in gas dangerous zones refer to GL Rules for<br />

Instrumentation (<strong>IV</strong>-7-6).<br />

G.2.6.9 Where pneumatically operated alarms are used the permanent supply of compressed air is to<br />

be safeguarded by suitable arrangements.<br />

G.3 Tightness of the protected space<br />

G.3.1 Apart from being provided with means of closing all ventilation openings and other openings in<br />

the boundaries of the protected space, special consideration shall be given to G.3.2 through G.3.4.<br />

G.3.2<br />

G.3.3<br />

A minimum agent holding time of 15 min shall be provided.<br />

The release of the system may produce significant over pressurization in the protected space.<br />

G.3.4 Escape routes which may be exposed to leakage from the protected space shall not be rendered<br />

hazardous during or after the discharge of the extinguishing gas. Control stations and other locations<br />

that require manning during a fire situation shall have provisions to keep the concentrations of products<br />

below values considered hazardous for the required duration of exposure.<br />

G.4 Warning signs and operating instructions<br />

G.4.1 Warning signs are to be provided at each access to and within a protected space as appropriate:<br />

• "WARNING! This space is protected by a fixed gas fire extinguishing system using .......... Do not enter<br />

when the alarm is actuated!"<br />

• "WARNING! Evacuate immediately upon sounding of the alarm of the gas fire extinguishing system."<br />

G.4.2<br />

Brief operating instructions are to be posted at the release stations.<br />

G.4.2.1 A comprehensive manual with the description of the system and maintenance instructions is to<br />

be provided. The manual shall contain an advice that any modifications to the protected space that alter<br />

the net volume of the space will render the approval for the individual installation invalid. In this case<br />

amended drawings and calculations have to be submitted to GL for approval.<br />

G.5 Documents<br />

Prior to commencing of the installation the following documents are to be submitted to GL for approval:<br />

• arrangement drawing of the protected space showing machinery, etc. in the space, and the location<br />

of nozzles, containers (modular system only) and release lines as applicable<br />

• list of volumes deducted from the gross volume<br />

• calculation of the net volume of the space and required supply of extinguishing gas<br />

Edition 2013 Germanischer Lloyd Page 8–12