(IV-7-3) General Safety
(IV-7-3) General Safety
(IV-7-3) General Safety
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Rules <strong>IV</strong> Industrial Services<br />
Part 7 Offshore Technology<br />
Chapter 3 <strong>General</strong> <strong>Safety</strong><br />
Section 8<br />
Active Fire Protection<br />
c) protective clothing of material to protect the skin from the heat radiating from the fire and from burns<br />
and scalding by steam. The outer surface shall be water resistant;<br />
d) boots and gloves of rubber or other electrically non-conducting material;<br />
e) a rigid helmet providing effective protection against impact;<br />
f) an electric safety lamp (hand lantern) of approved type with a capacity for at least three hours;<br />
g) an axe with high-voltage insulation to the satisfaction of GL.<br />
H.2.2 Number<br />
At least two fireman’s outfits shall be provided.<br />
H.2.3 Storage<br />
The fireman’s outfits have to be stored in a safe area, readily accessible and ready for use, in at least two<br />
locations as far apart from each other as practicable.<br />
H.2.4 Communication<br />
For internal communication one portable VHF radio set for each set of fireman’s equipment, for the fire<br />
fighting supervisor, the technical supervisor and the safety control center are to be provided.<br />
Edition 2013 Germanischer Lloyd Page 8–15