Rules <strong>IV</strong> Industrial Services<br />
Part 7 Offshore Technology<br />
Chapter 3 <strong>General</strong> <strong>Safety</strong><br />
Section 8<br />
Active Fire Protection<br />
Table 8.1<br />
Firefighting systems and equipment<br />
Areas and spaces to protected<br />
Permanently installed fire extinguishing<br />
systems<br />
CO 2<br />
Pressure water<br />
spraying system<br />
Foam system<br />
Connect. of firehoses<br />
Portable and mobile extinguishing<br />
equipment<br />
portable mobile<br />
Dry powder, 5<br />
kg<br />
CO2<br />
Dry powder,<br />
50 kg<br />
Foam, 45 liters<br />
Machinery spaces with<br />
internal combustion<br />
engines total outputs:<br />
Boiler rooms<br />
Spaces with<br />
electrical machinery,<br />
total output:<br />
< 750 kW 2 1<br />
> 360 kW 1 dry<br />
powder or 1 foam<br />
≥ 750 kW CO 2 or pressure water min. 2<br />
1<br />
system or high expansion<br />
1 dry powder or<br />
foam system<br />
2<br />
1 foam<br />
≥ 1.000 kW<br />
< 1.000 kW<br />
Oil filled equ.: CO 2 or deluge<br />
or foam<br />
min. 2<br />
3 2 1<br />
3 2<br />
Spaces for emergency diesels, aux.<br />
Diesel with > 750 kW<br />
CO 2 or pressure water system<br />
1<br />
Store rooms and galleys<br />
Galley: CO 2 in the hoods<br />
about stoves<br />
1<br />
1 in<br />
galley<br />
Acomodation areas<br />
Automatic sprinkler system<br />
1 every<br />
20 m +<br />
at each<br />
exit<br />
Control rooms with radio or electrical<br />
switchgear<br />
1 2<br />
Motor lifeboats 1 x 6 kg<br />
H.2 Fireman's outfits<br />
H.2.1 Type of outfit<br />
Each fireman’s outfit shall consist of at least:<br />
a) breathing apparatus of an approved type which may be either:<br />
• a smoke helmet or smoke mask which shall be provided with a suitable air pump and a length of air<br />
hose sufficient to reach from the open deck, well clear of doorway to any part of the machinery<br />
spaces. If, in order to comply with these Rules, an air hose exceeding 36 m in length would be necessary,<br />
a self-contained breathing apparatus shall be substituted or provided in addition as determined<br />
by GL, or<br />
• a self-contained compressed-air-operated breathing apparatus, the volume of air contained in the<br />
cylinders of which shall be at least 1200 l, or other self-contained breathing apparatus which shall be<br />
capable of functioning for at least 30 minutes.<br />
At least two spare fillings have to be provided for each breathing apparatus.<br />
b) a fire proof lifeline of sufficient length and strength, capable of being attached by means of a snaphook<br />
to the harness of the breathing apparatus or to a separate belt in order to prevent the breathing<br />
apparatus becoming detached when the lifeline is operated;<br />
Edition 2013 Germanischer Lloyd Page 8–14