Rules <strong>IV</strong> Industrial Services<br />

Part 7 Offshore Technology<br />

Chapter 3 <strong>General</strong> <strong>Safety</strong><br />

Section 8<br />

Active Fire Protection<br />

G.2.4.2.3 Duplicate sources of power located outside the protected space shall be provided for the release<br />

of the system and be immediately available, except that for machinery spaces, one of the sources<br />

of power may be located inside the protected space.<br />

G.2.4.2.4 Electric power circuits connecting the containers shall be monitored for fault conditions and<br />

loss of power. Visual and audible alarms shall be provided to indicate this.<br />

G.2.4.2.5 Pneumatic or hydraulic power circuits connecting the containers shall be duplicated. The<br />

sources of pneumatic or hydraulic pressure shall be monitored for loss of pressure. Visual and audible<br />

alarms shall be provided to indicate this.<br />

G.2.4.2.6 Within the protected space, electrical circuits essential for the release of the system shall be<br />

heat resistant, e.g. mineral-insulated cable or equivalent.<br />

Piping systems essential for the release of systems designed to be operated hydraulically or pneumatically<br />

shall be of steel.<br />

G.2.4.2.7 Not more than two discharge valves shall be fitted to any container.<br />

G.2.4.2.8 The containers shall be monitored for decrease in pressure due to leakage or discharge. Visual<br />

and audible alarms in the protected space and in the control station stand shall be provided to indicate<br />

this.<br />

G.2.4.2.9 Each container is to be fitted with an overpressure release device which under the action of<br />

fire causes the contents of the container to be automatically discharged into the protected space.<br />

G.2.5<br />

Piping and nozzles<br />

G.2.5.1 Wherever possible, pipe connections are to be welded. For detachable pipe joints, flange connections<br />

are to be used. For pipes with a nominal internal diameter of less than 50 mm threaded welding<br />

sockets may be employed. Threaded joints may be used only inside protected spaces.<br />

G.2.5.2 Flexible hoses may be used for the connection of containers to a manifold in centralised systems<br />

or to a rigid discharge pipe in modular systems. Hoses shall not be longer than necessary for this<br />

purpose and be type approved for the use in the intended installation.<br />

Hoses for modular systems are to be flame resistant.<br />

G.2.5.3 Only nozzles approved for use with the system shall be installed. The arrangement of nozzles<br />

shall comply with the parameters specified in the system's type approval Certificate, giving due consideration<br />

to obstructions. In the vicinity of passages and stairways nozzles shall be arranged such as to avoid<br />

personnel being endangered by the discharging gas.<br />

G.2.5.4<br />

The piping system shall be designed to meet the requirements stipulated in G.2.1.4.<br />

G.2.5.5 In piping sections where valve arrangements introduce sections of closed piping (manifolds<br />

with distribution valves), such sections shall be fitted with a pressure relief valve and the outlet of the<br />

valve shall be led to the open deck.<br />

G.2.6<br />

Release arrangements and alarms<br />

G.2.6.1 The system is to be designed for manual release only.<br />

If, in addition to manual release option also an automatic release is provided, suitable measures have to<br />

be implemented and approved by GL to ensure that no personal is present in the protected space when<br />

the gas is released.<br />

The controls for the manual release are to be arranged in lockable cabinets (release stations), the key<br />

being kept conspicuously next to the release station in a locked case with a glass panel. Separate release<br />

stations are to be provided for each space which can be flooded separately. The release stations shall be<br />

arranged near to the entrance of the protected space and shall be readily accessible also in case of a fire<br />

in the related space. Release stations shall be marked with the name of the space they are serving.<br />

G.2.6.2 Centralized systems shall be provided with additional means of releasing the system from the<br />

storage space.<br />

Edition 2013 Germanischer Lloyd Page 8–11