01.03.2014 Views

(IV-7-3) General Safety

(IV-7-3) General Safety

(IV-7-3) General Safety

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Rules <strong>IV</strong> Industrial Services<br />

Part 7 Offshore Technology<br />

Chapter 3 <strong>General</strong> <strong>Safety</strong><br />

Section 9<br />

Fire and Gas Detection Alarm Systems<br />

C.4 For areas provided with automatic pressure water spray systems, separate alarm loops per<br />

section are to be allocated.<br />

C.5 <strong>General</strong>ly the number of the detectors shall not exceed 20 per alarm loop. The number of detectors<br />

grouped in each loop within a machinery space should not exceed 10.<br />

C.6 Manually actuated alarms, i.e. Manual Alarm Call points (MAC), may be incorporated in a loop<br />

together with automatic alarms.<br />

C.7 The arrangement and number of fire detectors have to be such that all areas with an increased<br />

fire risk are covered. This applies in particular to Transformer and Reactor rooms/areas, Medium<br />

and High Voltage Switchgear Rooms, Machinery spaces (e.g. Generator enclosures/rooms and control<br />

and working spaces).<br />

C.8 Detectors should not be mounted close to ventilation outlets or in positions where the flow of<br />

air may affect their operation, or where they are liable to suffer mechanical damage.<br />

C.9 Ceiling-mounted detectors shall normally be located at least 0.5 m from walls.<br />

C.10 The maximum distance between detectors (and the maximum area monitored) shall not exceed<br />

the following figures:<br />

• for heat detectors: 9 m (37 m 2 )<br />

• for smoke detectors: 11 m (74 m 2 )<br />

The distance from walls shall not exceed<br />

• for heat detectors: 4.5 m<br />

• for smoke detectors: 5.5 m<br />

C.11 The installation of a type tested aspirating smoke detection (ASD) system can be approved by<br />

GL. The arrangement and setup of an ASD system shall be such that a detected fire can be clearly assigned<br />

to a fire zone.<br />

Concerning the arrangement and dimensioning of the sampling pipes of the ASD system the manufacturer<br />

requirements shall be strictly followed.<br />

D<br />

Public Address and <strong>General</strong> Alarm System<br />

D.1 Public address system<br />

D.1.1 In addition to the general emergency alarm a public address (PA) system is generally required<br />

on all normally or temporarily manned Offshore Substations. The PA system shall be operable from strategically<br />

important locations and from the central control station. It shall be audible throughout the accommodation<br />

area, at the crew’s normal working places and at the strategically important locations.<br />

D.1.2 If the public address system is used to transmit the general emergency alarm (PA/GA system),<br />

the following requirements shall be fulfilled:<br />

• The requirements for the general emergency alarm shall be satisfied.<br />

• At least two amplifiers are to be provided, each of them separately supplied and fused.<br />

• At least two loudspeaker circuits, supplied from separate amplifiers, are to be installed in each fire<br />

zone, respectively in its subdivisions.<br />

• The loudspeaker circuits are to be so arranged that transmission at a reduced loudness is maintained<br />

in the event of a failure of an amplifier or loudspeaker circuit.<br />

• Where loudspeakers with built-in volume controls are used, the volume controls must be disabled by<br />

the release of the alarm signal.<br />

Edition 2013 Germanischer Lloyd Page 9–3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!