Technical Data<br />
4.2 Mechanical Data<br />
XP10U-H4<br />
Display<br />
LCD graphical display, 3 LEDs<br />
Controls<br />
4-way key, 2 keys<br />
Interfaces<br />
Ethernet, USB, RS485, S0<br />
Fault signal relay<br />
Potential-free NO contact, 277 V/1 A<br />
Connections for AC PCB terminal<br />
PCB terminals inside the unit (max. cross section: 7 AWG)<br />
DC connections<br />
PCB terminals inside the unit (max. cross section: 11 AWG)<br />
Connection for Ethernet cable connection<br />
RJ45 connector<br />
Optional DC connection -<br />
Ambient temperature range [°F]<br />
-13 ... 140 (-25°C ... 60 °C)<br />
Storage temperature range [°F]<br />
-22 ... 158 (-30°C ... 70°C)<br />
Humidity range (non-condensing) [%] 0 ... 95<br />
Maximum installation elevation [ft above sea level] 6,561<br />
Temperature monitoring<br />
Yes<br />
Cooling<br />
Fan cooling<br />
Protection class NEMA 4<br />
Degree of contamination 2<br />
DC disconnect<br />
Built-in<br />
Housing<br />
Aluminum cast<br />
H x W x D [in]<br />
27.2 x 16.5 x 7.9 (690 x 420 x 200 mm)<br />
Total weight [lbs]<br />
88 (40 kg)<br />
Tabelle 2: Mechanical Data<br />