Installing the Inverter<br />

Authorised electrician<br />

NOTICE<br />

When the lead impedance is high (i.e. long grid-side leads), the voltage at the grid terminals of the<br />

inverter will increase during feed-in to the grid. The inverter monitors this voltage. If it exceeds the<br />

country-specific line overvoltage limit value, the inverter switches off.<br />

› Ensure that the lead cross-sections are sufficiently large or that the lead lengths are sufficiently<br />

short.<br />

Making the grid connection<br />

↻ Drill a hole for the AC leads into the connection board.<br />

1. Remove the outer cladding of the AC leads.<br />

2. Insert the AC leads through the hole into the connection area through the conduit pipe.<br />

3. Strip the insulation from the AC leads.<br />

4. Open the locks of the PCB terminals.<br />

5. Connect the leads in accordance with the labelling of the PCB terminals.<br />

6. Close the locks of the PCB terminals.<br />

7. Check that all connected leads are tightly seated.<br />

» The inverter is now connected to the power grid.<br />

NOTICE<br />

An AC-side disconnection unit must be provided in the final installation. This disconnection unit<br />

must installed in such a manner that access to it is possible at any time without hindrance.<br />

If a residual current circuit breaker is necessary due to the installation specification, then a type A AFI<br />

(AC/DC-sensitive residual current circuit breaker) must be used.<br />

7.3.2 Connecting the PV generator<br />

Connect the PV generator to the 4 DC positive and the 4 DC negative connection terminals in the connection area<br />

of the inverter.<br />

DANGER<br />

Risk of fatal injury due to contact voltages.<br />

› During installation: Electrically disconnect the DC positive and DC negative from the protective<br />

earth (PE).<br />

Removing the connection without previously disconnecting the inverter from the DC generator can<br />

result in a hazard to health and damage to the inverter.<br />

WARNING<br />

No internal GFDI.<br />

This unit is not provided with a GFDI (ground-fault detector-interrupter). The inverter must be used<br />

with an external GFDI device as required by the article 690 of the national electrical code for the<br />

installation location.<br />

Page 18 <strong>Installation</strong> <strong>Instructions</strong> blueplanet XP10U-H4