Installing the Inverter<br />

Authorised electrician<br />

7.3.2.6 Connecting the PV generator<br />

DANGER<br />

Risk of fatal injury due to electric shock<br />

Severe injuries or death will result if the live connections are touched. When there is irradiance, DC<br />

voltage is present on the open ends of the DC leads.<br />

› Do not touch the open ends of the leads.<br />

› Avoid short circuits.<br />

Connecting the PV generator<br />

↻ Drill one hole for each DC negative and DC positive lead into the connection board.<br />

1. Remove the outer cladding of the DC leads.<br />

2. Insert the DC leads into the connection area through the conduit pipes.<br />

3. Strip the insulation from the DC leads.<br />

4. Connect the leads to the PCB terminals in accordance with the labelling.<br />

» The inverter is connected to the PV generator.<br />

7.3.3 Grounding the housing<br />

An optional grounding of the housing is possible at the grounding point provided for that purpose in the connection<br />

area of the inverter. Please observe any national installation regulations in this regard.<br />

Ground the housing of the inverter, if necessary, at the grounding point provided for that purpose in the connection<br />

area of the inverter. It is marked with the symbol.<br />

Figure 11: Grounding point in the connection area<br />

Grounding the housing<br />

↻ Drill a hole for the grounding lead into the connection board.<br />

1. Remove the outer cladding from the grounding lead.<br />

2. Insert the grounding lead into the connection area through the conduit pipe.<br />

3. Remove the insulation from the grounding lead.<br />

4. Furnish the stripped lead with an M6 ring cable lug.<br />

5. Screw the ring cable lug to the grounding point with an M6 screw.<br />

6. Check for firm seating of the lead.<br />

7.4 Connecting the interfaces<br />

All interface connectors are located on the connection board. Drill holes for the conduits into the connection<br />

board.<br />