Installing the Inverter<br />
Authorised electrician<br />
7.3.2.6 Connecting the PV generator<br />
DANGER<br />
Risk of fatal injury due to electric shock<br />
Severe injuries or death will result if the live connections are touched. When there is irradiance, DC<br />
voltage is present on the open ends of the DC leads.<br />
› Do not touch the open ends of the leads.<br />
› Avoid short circuits.<br />
Connecting the PV generator<br />
↻ Drill one hole for each DC negative and DC positive lead into the connection board.<br />
1. Remove the outer cladding of the DC leads.<br />
2. Insert the DC leads into the connection area through the conduit pipes.<br />
3. Strip the insulation from the DC leads.<br />
4. Connect the leads to the PCB terminals in accordance with the labelling.<br />
» The inverter is connected to the PV generator.<br />
7.3.3 Grounding the housing<br />
An optional grounding of the housing is possible at the grounding point provided for that purpose in the connection<br />
area of the inverter. Please observe any national installation regulations in this regard.<br />
Ground the housing of the inverter, if necessary, at the grounding point provided for that purpose in the connection<br />
area of the inverter. It is marked with the symbol.<br />
Figure 11: Grounding point in the connection area<br />
Grounding the housing<br />
↻ Drill a hole for the grounding lead into the connection board.<br />
1. Remove the outer cladding from the grounding lead.<br />
2. Insert the grounding lead into the connection area through the conduit pipe.<br />
3. Remove the insulation from the grounding lead.<br />
4. Furnish the stripped lead with an M6 ring cable lug.<br />
5. Screw the ring cable lug to the grounding point with an M6 screw.<br />
6. Check for firm seating of the lead.<br />
7.4 Connecting the interfaces<br />
All interface connectors are located on the connection board. Drill holes for the conduits into the connection<br />
board.<br />