4.5.5.2<br />

The monitor circuitry shall switch the +5 VDC Standby ON immediately upon Power<br />

Failure and isolate (OFF) the line at Power Up.<br />

4.5.5.3<br />

The 60 Hz Square Wave LINESYNC signal shall be generated by a crystal oscillator,<br />

which shall be synchronized to the 60-Hz VAC incoming power line at 120 and 300<br />

degrees. A continuous square wave signal shall be +5 VDC amplitude, 8.333 ms halfcycle<br />

pulse duration, and 50 ±1% duty cycle. The output shall have drive sink capability<br />

<strong>of</strong> 16 mA. A 2 K-Ohm pull-up resistor shall be connected between the output and +5<br />

VDC. The monitor circuit shall compensate for missing pulses and line noise during<br />

normal operation.<br />

4.5.5.4<br />

The LINESYNC shall continue until SYSRESET transitions LOW and begin when<br />

SYSRESET transitions HIGH.<br />

4.5.6 Power Supply Requirements<br />

Voltage Tolerances I Minimum I Maximum<br />

+5 VDC<br />

+4.875 to +5.125<br />

10.0 AMP - MODULE 2070-4A<br />

1.0 AMP<br />

VDC<br />

3.5 AMP – MODULE 2070-4B<br />

+12 VDC Serial +11. 4 to +12. 6 VDC 0.1 AMP 0.5 AMP<br />

-12 VDC Serial -11. 4 to –12. 6 VDC 0.1 AMP 0.5 AMP<br />

+12 VDC +11. 4 to +12. 6 VDC 0.1 AMP 1.0 AMP<br />

4.5.6.1 Line Regulation<br />

Line Regulation shall meet the table tolerance values for voltage range <strong>of</strong> 90 to 135 VAC,<br />

the maximum/minimum loads called out in the table and including ripple noise.<br />

4.5.6.2 Load Regulation<br />

Load Regulation shall meet the table tolerance values for voltage range <strong>of</strong> 90 to 135<br />

VAC, the maximum/minimum loads called out in the table and including ripple noise.<br />

4.5.6.3 Efficiency<br />

70 % minimum.<br />

4.5.6.4 Ripple & noise<br />

Standard for the ATC – Type 2070 March 29, 2001<br />